{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-7LK13","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-7LK13","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-7LK13","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-7LK13","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV1 series RCBO, 1P+N, 13 A rated at 30 °C, 6 kA breaking capacity per EN 60898, Type A fault current, tripping characteristic C, short-time delayed G / super resistant K design, 18 mm wide, IP20 with distribution board installed.","salesMarkdown":"The Siemens 5SV1316-7LK13 is a SENTRON RCBO — a combined residual-current and overcurrent protective device — in a 1P+N configuration, rated 230 V AC, 50/60 Hz. It carries 13 A at 30 °C (thermal derating curve provided down to 10.01 A at 70 °C), with a 6 kA breaking capacity per EN 60898. The Type A fault-current sensing catches pulsating DC residual currents, and the C characteristic handles moderate inrush from motor or lighting loads. It is a short-time delayed G / super resistant K design, meaning it tolerates brief surge currents better than a standard RCBO — relevant for panels feeding compressors or pumps that start hard. Installation depth is 70 mm — verify gland-plate clearance inside the enclosure. This is a panel-interior device, not a field-mounted unit. Pollution degree 2 (normal industrial environment). Energy limiting class 3.","metaTitle":"Siemens 5SV1316-7LK13 SENTRON RCBO, 1P+N, 13 A, 6 kA, Type A","metaDescription":"Siemens 5SV1316-7LK13 SENTRON RCBO, 1P+N, 13 A rated at 30 °C, 6 kA breaking capacity per EN 60898, Type A fault current, tripping characteristic C, 18 mm wide. Quoted to order aga","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","at 30 Cel":"13 A","at 40 Cel":"12.35 A","at 45 Cel":"11.96 A","at 50 Cel":"11.57 A","at 55 Cel":"11.18 A","at 60 Cel":"10.79 A","at 65 Cel":"10.4 A","at 70 Cel":"10.01 A","Halogen-Free":"Yes","Silicon-Free":"Yes","Number of poles":"2","Type of voltage":"AC","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Degree of pollution":"2","Operating frequency":"50/60 Hz","Product designation":"RCBO","Protection class IP":"IP20, if the distribution board is installed, with connected conductors","at AC / rated value":"230 V","Overvoltage category":"III","Design of the product":"Short-time delayed G, super resistant K","Energy limiting class":"3","Number of width units":"1","Type of fault current":"A","Number of poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","circuit-breaker / Design":"5SV1","Tripping characteristic class":"C","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / of power supply cord":"Either top or bottom","Number of poles / with protection":"1","acc. to IEC 60947-2 / rated value":"10 kA","Product feature / Touch protection":"Yes","Supply voltage frequency / rated value":"50 Hz","Operating current / at AC / rated value":"13 A","Tripping residual current / rated value":"30 mA","Influence of the surrounding temperature":"Max. 95% humidity","Surge current resistance / at (8/20) μs":"3 kA","Product function / neutral conductor switching":"Yes","Mechanical service life (switching cycles) / typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027056&mlfb=5SV1316-7LK13","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV1316-7LK13/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SV1316-7LK13 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 5SV1316-7LK13's listed depth?","answer":"Depth is 77 mm (installation depth 70 mm). Width is 18 mm (one width unit), height 90 mm."},{"question":"What compliance documentation does this brand provide for 5SV1316-7LK13?","answer":"The manufacturer provides RoHS, REACH, and relevant IEC/EN compliance documentation upon request. The part carries a 6 kA breaking capacity rating per EN 60898 and is classified per DIN EN 61346-2 / 81346-2 with function code F."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-7LK13","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-7LK13 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}