{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1316-7LK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1316-7LK16","canonicalUrl":"https://aoctrl.com/siemens/5SV1316-7LK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1316-7LK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV1316-7LK16 RCBO, 1P+N, 16 A rated, 30 mA residual current, Type A, tripping characteristic C, 6 kA breaking capacity, 1 modular width.","salesMarkdown":"## RCBO for final-circuit protection The Siemens 5SV1316-7LK16 is a 1P+N RCBO (residual current circuit breaker with overcurrent protection) from the SENTRON series, combining a 16 A overcurrent trip with a 30 mA residual-current device in a single 18 mm wide module. Type A residual-current detection handles pulsating DC fault currents, so it is specified for circuits with single-phase rectifiers, switched-mode power supplies, or electronic loads where a pure AC-sensitive (Type AC) device would be blind. Rated 16 A at 30 °C ambient, the continuous current must be derated as panel temperature rises: 15.2 A at 40 °C, 14.72 A at 45 °C, 14.24 A at 50 °C, 13.76 A at 55 °C, 13.28 A at 60 °C, 12.8 A at 65 °C, and 12.32 A at 70 °C (–). Supply can enter from either top or bottom; mounting position is any orientation. The IP20 rating applies only when the distribution board is installed with connected conductors — not a standalone outdoor device.","metaTitle":"Siemens 5SV1316-7LK16 SENTRON RCBO 16A 30mA Type A C-Char 6k","metaDescription":"Siemens 5SV1316-7LK16 SENTRON RCBO, 16A rated, 30mA residual current, Type A, C characteristic, 6kA breaking capacity, 1 MW wide. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50/60 Hz","Product Designation":"RCBO","at AC / rated value":"16 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Short-time delayed G, super resistant K","Residual Current Type":"A","Energy Limitation Class":"3","Weight / With Packaging":"133 g","according to EN 61346-2":"F","at 30 °C / rated value":"16 A","at 40 °C / rated value":"15.2 A","at 45 °C / rated value":"14.72 A","at 50 °C / rated value":"14.24 A","at 55 °C / rated value":"13.76 A","at 60 °C / rated value":"13.28 A","at 65 °C / rated value":"12.8 A","at 70 °C / rated value":"12.32 A","according to IEC 81346-2":"F","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","according to EN 60898 / rated value":"6 kA","Tripping Fault Current / Rated Value":"30 mA","insulation voltage (Ui) / rated value":"253 V","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Voltage Resistance / Rated Value":"4 000 V","according to IEC 60947-2 / rated value":"10 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Surge Current Resistance / At (8/20) μS":"3 kA","Type Of Voltage / Of The Operating Voltage":"AC","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/50e590cfc611663d86f4d47f5958db69.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027057&mlfb=5SV1316-7LK16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV1316-7LK16/alternatives.json"},"ai":{"faq":[{"question":"What is the rated current and residual trip of 5SV1316-7LK16?","answer":"Rated 16 A overcurrent with a 30 mA residual-current trip, Type A, C characteristic, 6 kA breaking capacity per EN 60898."},{"question":"How do I get current pricing and availability for 5SV1316-7LK16?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time; the part is sourced to order through independent distribution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1316-7LK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1316-7LK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}