{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1613-1KK06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1613-1KK06","canonicalUrl":"https://aoctrl.com/siemens/5SV1613-1KK06","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1613-1KK06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 5SV1613-1KK06, 1P+N, 6 A rated, C characteristic, 300 mA residual current, 4.5 kA breaking capacity, 18 mm width, 77 mm depth.","salesMarkdown":"The C-curve means it holds through motor inrush and capacitive loads that would nuisance-trip a B-curve, but trips fast on a hard short — standard choice for general-purpose socket outlets and small equipment feeds. At 40 °C it derates to 5.64 A, at 50 °C to 5.28 A, and at 70 °C to 4.44 A — so if this lives in a hot panel near a drive or transformer, size the load accordingly. The 300 mA residual current is an AC-type trip (sine-wave faults only), not A-type (pulsating DC) or F-type (mixed-frequency). That matters: if the downstream load includes a VFD, LED driver, or single-phase rectifier that can produce smooth DC fault current, an AC-type RCBO may not trip within the required time. Verify the load's fault signature before committing this to the BOM. The 1P+N design switches the line conductor only; the neutral is switched but not protected against overcurrent. Two physical poles, one with overcurrent protection. That is standard for single-phase final circuits where the neutral is not fused. The 18 mm width (1 modular unit) saves DIN rail space — you can pack 12 of these per 12-module enclosure row. Mounts in any position on DIN rail. Depth is 77 mm (70 mm installation depth), so it fits standard distribution boards with 80 mm+ internal depth. Halogen-free and silicon-free construction, which matters for panels in high-fire-risk zones (tunnels, data centers) where corrosive gas from a fault must be minimized.","metaTitle":"Siemens 5SV1613-1KK06 SENTRON RCBO, 6 A, C-curve, 300 mA, 1P","metaDescription":"Siemens SENTRON 5SV1613-1KK06 RCBO, 6 A rated, C tripping characteristic, 300 mA residual current, 4.5 kA breaking capacity, 1P+N, 18 mm wide. Active production. Sourced to order a","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1613-1KK06","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO compact 1P+N 4.5 kA type AC 300 mA C6","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"6 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","Weight With Packaging":"133 g","at 30 °C rated value":"6 A","at 40 °C rated value":"5.64 A","at 45 °C rated value":"5.46 A","at 50 °C rated value":"5.28 A","at 55 °C rated value":"5.04 A","at 60 °C rated value":"4.86 A","at 65 °C rated value":"4.62 A","at 70 °C rated value":"4.44 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"4.5 kA","Tripping Fault Current Rated Value":"300 mA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"5 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","Mechanical Service Life (Operating Cycles) Typical":"10 000","for rated value of the current at AC in hot operating state per pole":"0.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aec721310ef05fac2c433250b4945b14.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027064&mlfb=5SV1613-1KK06"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SV1613-1KK06?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through our independent distribution network — no stock count or price is published here."},{"question":"What is 5SV1613-1KK06's listed depth (77 mm) on this component line?","answer":"The product depth is 77 mm, with an installation depth of 70 mm. This fits standard distribution boards with at least 80 mm internal depth."},{"question":"What is 5SV1613-1KK06's listed width (18 mm) on this component line?","answer":"The width is 18 mm, which is 1 modular unit (1 MW). This allows 12 units per 12-module enclosure row."},{"question":"What compliance documentation does this brand provide for 5SV1613-1KK06 (RoHS, REACH, UL, IEC)?","answer":"The product is designed to EN 60898 (breaking capacity 4.5 kA) and carries IEC ratings for overvoltage category III and pollution degree 2. It is halogen-free and silicon-free. For specific RoHS, REACH, or UL documentation, request the manufacturer's declaration with your RFQ."},{"question":"Will 5SV1613-1KK06 drop into a panel that was specified around 5SL6120-7 without rewiring?","answer":"Not directly. The 5SV1613-1KK06 is an RCBO (combined overcurrent and residual current protection), while the 5SL6120-7 is a standalone MCB (overcurrent only). The RCBO is wider (1 MW vs 1 MW for the MCB, but the RCBO includes the RCD module in the same width — no extra space needed). However, the residual current function adds a neutral connection requirement that the MCB-only circuit may not have wired. Check the panel wiring before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1613-1KK06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1613-1KK06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}