{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1616-0KK06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1616-0KK06","canonicalUrl":"https://aoctrl.com/siemens/5SV1616-0KK06","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1616-0KK06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV1616-0KK06 RCBO, 6 A rated, B curve, 1P+N, 6 kA (EN 60898) / 35 kA (IEC 60947-2), residual current type AC, 18 mm wide, IP20.","salesMarkdown":"It protects against both overload/short-circuit and earth leakage in one unit, saving a DIN-rail slot over separate devices. The residual-current element is type AC, meaning it detects sinusoidal AC earth faults only. For a line with pulsed DC or mixed-frequency fault currents (variable-speed drives, UPS-fed circuits), you would need a type A or F device instead. The 5SV1616-0KK06 carries two breaking-capacity ratings: 6 kA per EN 60898 (the standard for household-type MCBs) and 35 kA per IEC 60947-2 (the industrial standard for circuit-breakers). The 35 kA figure applies when the device is used as an industrial breaker per 60947-2, giving headroom for high-fault installations. The 6 kA rating governs most residential and light-commercial panels. That matters for selectivity coordination with upstream breakers. Compared to the 5SY6006-7 (a standard MCB without RCD), the 5SV1616-0KK06 adds the residual-current module in the same footprint. If your panel was wired for a 5SY6006-7, this RCBO drops into the same 18 mm slot and same busbar arrangement — no rewiring needed for the phase connection, but the neutral must be routed through the RCBO for the RCD to work. ## Temperature derating — real-world current capacity Above that, the device derates: 5.64 A at 40 °C, 5.28 A at 50 °C, and down to 4.44 A at 70 °C. If the panel runs warm (enclosed DIN-rail assembly, adjacent heat sources), size the load to the derated value at your ambient — not the 30 °C number. That simplifies panel layout when busbar routing forces a reverse feed. The 7 mm difference accounts for the front toggle and terminal screws. Verify the enclosure depth clears 77 mm plus wiring bend radius.","metaTitle":"Siemens 5SV1616-0KK06 SENTRON RCBO, 6 A, B Curve, 1P+N, 6 kA","metaDescription":"Siemens 5SV1616-0KK06 SENTRON RCBO, 6 A rated, B tripping characteristic, 1P+N, 6 kA breaking capacity per EN 60898. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1616-0KK06","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO compact 1P+N 6 kA type AC 300 mA B6","Halogen-Free":"Yes","Silicon-Free":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","acc. to IEC 81346-2":"F","at AC / rated value":"6 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","Number Of Poles / Note":"1P+N","acc. to DIN EN 61346-2":"F","Energy Limitation Class":"3","Weight / With Packaging":"133 g","at 30 °C / rated value":"6 A","at 40 °C / rated value":"5.64 A","at 45 °C / rated value":"5.46 A","at 50 °C / rated value":"5.28 A","at 55 °C / rated value":"5.04 A","at 60 °C / rated value":"4.86 A","at 65 °C / rated value":"4.62 A","at 70 °C / rated value":"4.44 A","Number Of Modular Width Units":"1","Tripping Characteristic Class":"B","acc. to EN 60898 / rated value":"6 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"Either top or bottom","Number Of Poles / With Protection":"1","acc. to IEC 60947-2 / rated value":"35 kA","Product Feature / Touch Protection":"Yes","Tripping Fault Current / Rated Value":"300 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Influence Of The Surrounding Temperature":"Max. 95% humidity","Product Function / Neutral Conductor Switching":"Yes","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aec721310ef05fac2c433250b4945b14.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027086&mlfb=5SV1616-0KK06"},"ai":{"faq":[{"question":"What is the breaking capacity of 5SV1616-0KK06?","answer":"6 kA per EN 60898 and 35 kA per IEC 60947-2. The 35 kA rating applies when used as an industrial circuit-breaker per 60947-2."},{"question":"Will 5SV1616-0KK06 drop into a panel that was specified around 5SY6006-7 without rewiring?","answer":"Yes, it fits the same 18 mm DIN-rail slot and busbar arrangement. However, the neutral must be routed through the RCBO for the RCD to function — a standard MCB like 5SY6006-7 does not require a neutral connection through the device."},{"question":"What is the temperature derating for 5SV1616-0KK06?","answer":"Rated 6 A at 30 °C, derated to 5.64 A at 40 °C, 5.28 A at 50 °C, and 4.44 A at 70 °C. Size the continuous load to the derated value at your panel ambient."},{"question":"Where can I buy 5SV1616-0KK06?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1616-0KK06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1616-0KK06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}