{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV1616-7KK02","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV1616-7KK02","canonicalUrl":"https://aoctrl.com/siemens/5SV1616-7KK02","factsUrl":"https://aoctrl.com/api/mcp/products/5SV1616-7KK02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCBO, 2 A rated, C-curve, 300 mA Type A residual current, 6 kA breaking capacity, 1P+N, 1 MW width, IP20.","salesMarkdown":"The Siemens 5SV1616-7KK02 is a SENTRON RCBO — a combined overcurrent and residual-current circuit breaker in a single 18 mm-wide module (1 MW). It protects a single-phase final subcircuit against overload, short-circuit, and earth leakage, with a 2 A rated current, C-curve tripping characteristic, and a 300 mA Type A residual-current trip. The 300 mA residual-current threshold is a Type A device, so it detects pulsating DC fault currents as well as sinusoidal AC — important for electronics-fed circuits (VFDs, switched-mode supplies). The 6 kA breaking capacity is the maximum prospective fault current the device can safely interrupt; it matches the typical 6 kA rating of domestic distribution boards. Note the 50 Hz only rating — not suitable for 60 Hz systems. ## Temperature derating and installation Above that, derate progressively: 1.9 A at 40 °C, 1.8 A at 50 °C, 1.7 A at 60 °C, and 1.6 A at 70 °C (–). In a crowded DIN-rail enclosure with poor airflow, the effective current capacity may be lower than the label.","metaTitle":"Siemens 5SV1616-7KK02 SENTRON RCBO, 2 A C-curve, 300 mA Type","metaDescription":"Siemens SENTRON RCBO 5SV1616-7KK02: 2 A rated, C-curve, 300 mA Type A residual current, 6 kA breaking capacity (EN 60898). 1 MW wide, IP20. In active production. Sourced to order;","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77 mm","Width":"18 mm","title":"5SV1616-7KK02","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"RCBO compact 1P+N 6 kA type A 300 mA C2","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Mounting Position":"any","at AC rated value":"2 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Operating Frequency":"50 Hz","Product Designation":"RCBO","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","Weight With Packaging":"133 g","at 30 °C rated value":"2 A","at 40 °C rated value":"1.9 A","at 45 °C rated value":"1.86 A","at 50 °C rated value":"1.8 A","at 55 °C rated value":"1.76 A","at 60 °C rated value":"1.7 A","at 65 °C rated value":"1.66 A","at 70 °C rated value":"1.6 A","Energy Limitation Class":"3","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"Either top or bottom","Tripping Characteristic Class":"C","Number Of Poles With Protection":"1","according to EN 60898 rated value":"6 kA","Tripping Fault Current Rated Value":"300 mA","insulation voltage (Ui) rated value":"253 V","Supply Voltage Frequency Rated Value":"50 Hz","Surge Voltage Resistance Rated Value":"4 000 V","according to IEC 60947-2 rated value":"10 kA","Surge Current Resistance At (8/20) μS":"1 kA","Influence Of The Surrounding Temperature":"Max. 95% humidity","Type Of Voltage Of The Operating Voltage":"AC","for rated value of the current at AC in hot operating state per pole":"0.65 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aec721310ef05fac2c433250b4945b14.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1027102&mlfb=5SV1616-7KK02"},"ai":{"faq":[{"question":"Where can I buy 5SV1616-7KK02 and how do I get a price?","answer":"The part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — figures are confirmed at quote time."},{"question":"What is the closest functional second-source for 5SV1616-7KK02?","answer":"The closest functional peer is the 5SU9354-7KK16, also a SENTRON RCBO with similar ratings. However, verify the physical dimensions and terminal layout — the 5SV1616-7KK02 is 18 mm wide (1 MW) and the 5SU9354-7KK16 may differ in width or depth. Always compare the mounting footprint before substituting."},{"question":"What is 5SV1616-7KK02's listed depth?","answer":"The depth is 77 mm, with an installation depth of 70 mm behind the panel."},{"question":"What is 5SV1616-7KK02's listed width?","answer":"The width is 18 mm, which corresponds to 1 modular width unit (MW) on a DIN rail."},{"question":"Will 5SV1616-7KK02 drop into a panel specified around 5SU9354-7KK16 without rewiring?","answer":"Not necessarily. Both are SENTRON RCBOs, but the 5SU9354-7KK16 may have a different width or depth. The 5SV1616-7KK02 is 18 mm wide (1 MW) and 77 mm deep. Check the panel cut-out and DIN-rail space against the alternative part's dimensions before direct substitution."},{"question":"What compliance documentation does Siemens provide for 5SV1616-7KK02?","answer":"The part is halogen-free and silicon-free. It carries a pollution degree 2 rating and overvoltage category III. The manufacturer typically provides RoHS, REACH, and CE declarations; check the product documentation for specific UL or IEC certificates."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV1616-7KK02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV1616-7KK02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}