{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3111-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3111-6","canonicalUrl":"https://aoctrl.com/siemens/5SV3111-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3111-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3111-6, 2-pole Type A RCCB, 16 A rated, 10 mA sensitivity, 230 V AC, 50 Hz, 10 kA SCCR, DIN rail mount, active.","salesMarkdown":"The 5SV3111-6: The 10 mA sensitivity on a Type A RCCB means this unit detects sinusoidal AC residual currents plus pulsating DC residuals — common in modern electronics, variable-speed drives, and switched-mode power supplies. It is instantaneous (no short-time delay), so it trips on the first half-cycle of a fault, which is appropriate for circuits where nuisance tripping from transient surges is not expected. The 10 kA short-circuit current rating (SCCR) is the maximum prospective fault current the device can safely interrupt under IEC 60898-1. The device also carries a 0.5 kA rating according to IEC 61008-1, which governs the RCCB's performance under specific test conditions. For a main RCCB that sees infrequent operation, this is more than adequate; for a frequently switched load, consider the electrical life (not stated here) which is usually lower. Depth is 70 mm, installation depth matches at 70 mm, height is 90 mm. Mounts in any position, supply can enter from top or bottom. The IP20 rating applies only when the distribution board is installed and conductors are connected — bare terminals are not finger-safe. Silicon-free construction, which matters for applications like automotive paint shops or semiconductor fabs where silicone outgassing can cause adhesion or contamination issues.","metaTitle":"Siemens SENTRON 5SV3111-6 RCCB, 2-pole, 16 A, 10 mA, 230 V","metaDescription":"Siemens SENTRON 5SV3111-6 residual current circuit breaker, 2-pole type A, 16 A, 10 mA, 230 V AC, 50 Hz, 10 kA SCCR, active production, DIN rail mount.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Grid Spacing":"60 mm","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"top or bottom","according to IEC 61008-1 rated value":"0.5 kA","Switching Function Short-Term Delayed":"No","Value Range Of The Operating Frequency":"50 Hz","value range of the supply voltage at AC":"230 V","Ambient Temperature During Storage Minimum":"-40 °C","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"100 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","Short-Circuit Current Of Series Fuse Maximum Permissible":"63 A","for rated value of the current at AC in hot operating state per pole":"0.7 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$154.83","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=268753&mlfb=5SV3111-6","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV3111-6/alternatives.json"},"ai":{"faq":[{"question":"Will 5SV3111-6 drop into a panel specified around 5SL4363-7 without rewiring?","answer":"No — the 5SL4363-7 is 54 mm wide (3 modular units) and 76 mm deep, while the 5SV3111-6 is 36 mm wide (2 modular units) and 70 mm deep. The footprint and function differ; rewiring and panel layout changes would be required."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3111-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3111-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}