{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3311-6GV01","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3311-6GV01","canonicalUrl":"https://aoctrl.com/siemens/5SV3311-6GV01","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3311-6GV01","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3311-6GV01, 2-pole RCCB, 16 A rated, 30 mA trip, Type A, 10 kA SCCR, 230 V AC, 50 Hz, DIN rail mount, IP20.","salesMarkdown":"The Siemens SENTRON 5SV3311-6GV01 is a 2-pole residual current circuit breaker (RCCB) rated 16 A at 230 V AC, 50 Hz, with a 30 mA trip threshold and Type A residual current sensitivity. Type A detects sinusoidal AC and pulsating DC residual currents — the standard choice for circuits feeding single-phase electronics, switched-mode power supplies, and appliances with rectifier front ends. Instantaneous design (no intentional delay) trips within the standard RCCB response window. Depth is 70 mm, height 90 mm. Mounting position is unrestricted — install top or bottom feed, any orientation. IP20 with connected conductors in a distribution board; overvoltage category III suits fixed-installation mains-side use. Silicon-free construction avoids outgassing concerns in sensitive contact environments. ## Thermal performance and derating The flat current curve simplifies panel design: no temperature-based ampacity reduction in typical enclosure conditions.","metaTitle":"Siemens SENTRON 5SV3311-6GV01 RCCB, 2-pole, 16 A, 30 mA, Typ","metaDescription":"Siemens SENTRON 5SV3311-6GV01 2-pole RCCB, 16 A rated, 30 mA trip, Type A, 10 kA SCCR, 230 V AC, 50 Hz. DIN rail mount, IP20. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV3311-6GV01","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, type A, In: 16 A, 30 mA, Un AC: 230 V, Bulk packaging 36 units","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"16 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"Bulk packaging 36 units","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","I2t value permissible":"58 000 A²·s","Residual Current Type":"A","at 40 °C rated value":"16 A","at 45 °C rated value":"16 A","at 50 °C rated value":"16 A","at 55 °C rated value":"16 A","at 60 °C rated value":"16 A","at 65 °C rated value":"16 A","at 70 °C rated value":"16 A","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"top or bottom","Let-Through Current Permissible":"5 200 A","Tripping Fault Current Rated Value":"30 mA","Surge Current Resistance Rated Value":"1 kA","according to IEC 61008-1 rated value":"0.5 kA","Switching Function Short-Term Delayed":"No","Value Range Of The Operating Frequency":"50 Hz","value range of the supply voltage at AC":"230 V","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"195 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","Short-Circuit Current Of Series Fuse Maximum Permissible":"63 A","for rated value of the current at AC in hot operating state per pole":"0.4 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ae044d717fa46f768b85cb2eedb08a59.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=572866&mlfb=5SV3311-6GV01"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3311-6GV01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3311-6GV01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}