{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3311-6KK12","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3311-6KK12","canonicalUrl":"https://aoctrl.com/siemens/5SV3311-6KK12","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3311-6KK12","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3311-6KK12, 2-pole RCCB, Type A, 16 A rated, 30 mA trip sensitivity, 230 V AC, 10 kA short-circuit capacity, SIGRES variant for harsh ambient conditions.","salesMarkdown":"The Siemens 5SV3311-6KK12 is a 2-pole residual current circuit breaker (RCCB) from the SENTRON family, Type A, rated 16 A with 30 mA trip sensitivity on a 230 V AC, 50 Hz supply. It is an instantaneous-trip device — no intentional short-time delay — so it responds immediately to earth leakage currents above the threshold. This part carries the SIGRES designation for harsh ambient conditions, meaning the internal design tolerates condensation, vibration, and aggressive atmospheres better than a standard RCCB — relevant for outdoor enclosures, agricultural sheds, or unheated plant rooms. Supply can be connected from top or bottom; for SIGRES function, top feed is recommended to maintain protection even when the device is switched off. The IP20 rating applies when installed in a distribution board with conductors connected — standard for panel-internal protection, not for wet-area standalone use. The 30 mA sensitivity is standard for personnel protection, catching leakage through the human body. Type A detection covers sinusoidal AC and pulsating DC residual currents. The part is silicon-free. Power dissipation is 0.7 W per pole at rated current. Occupies 2 MW (36 mm) on a 60 mm grid-spaced DIN rail. The 70 mm depth fits standard 80 mm deep enclosures with clearance for wiring. The overvoltage category is III (fixed installation, distribution level), so it is rated for the transient environment of a building main panel or industrial sub-distribution board.","metaTitle":"Siemens 5SV3311-6KK12 SENTRON RCCB, 2-pole, 16 A, 30 mA, Typ","metaDescription":"Siemens 5SV3311-6KK12 SENTRON RCCB, 2-pole, Type A, 16 A, 30 mA, 230 V AC, 10 kA SCCR, IP20. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV3311-6KK12","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, type A, In: 16 A, 30 mA, Un AC: 230 V, SIGRES (harsh ambient conditions)","Grid Spacing":"60 mm","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"SIGRES (harsh ambient conditions)","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"top or bottom (top for SIGRES function also in switched-off state)","according to IEC 61008-1 rated value":"0.5 kA","Switching Function Short-Term Delayed":"No","Value Range Of The Operating Frequency":"50 Hz","value range of the supply voltage at AC":"230 V","Ambient Temperature During Storage Minimum":"-40 °C","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"195 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","Short-Circuit Current Of Series Fuse Maximum Permissible":"80 A","for rated value of the current at AC in hot operating state per pole":"0.7 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/143a375c8c02e7cdbb58cff151fccdec.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=576188&mlfb=5SV3311-6KK12"},"ai":{"faq":[{"question":"What is 5SV3311-6KK12's listed depth and width?","answer":"Depth is 70 mm, width is 36 mm (2 modular width units), height is 90 mm. These dimensions match the standard SENTRON 2-pole RCCB footprint and fit a 60 mm grid-spaced DIN rail."},{"question":"Will 5SV3311-6KK12 drop into a panel specified around 5SL4363-7 without rewiring?","answer":"No — the 5SL4363-7 is a 3-pole miniature circuit breaker (MCB) with a 54 mm width and different function. The 5SV3311-6KK12 is a 2-pole RCCB at 36 mm width. They are not footprint-compatible and serve different protection roles (earth leakage vs overcurrent). Stick with the specified RCCB order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3311-6KK12","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3311-6KK12 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}