{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3314-6GV01","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3314-6GV01","canonicalUrl":"https://aoctrl.com/siemens/5SV3314-6GV01","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3314-6GV01","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3 series, 5SV3314-6GV01 RCCB, 40 A rated, 230 V AC, 2-pole, Type A, instantaneous, 10 kA short-circuit rating, DIN rail mount.","salesMarkdown":"It carries a 10 kA short-circuit current rating (Icn) and is designed for instantaneous tripping — no intentional delay, so it clears fast on earth faults. Type A detection means this RCCB handles both sinusoidal AC residual currents and pulsating DC — the kind rectifier-fed loads (VFDs, switching power supplies, LED drivers) can produce. If your downstream equipment includes single-phase rectification, Type A is the correct choice; a standard AC-type RCCB may not trip on pulsating DC faults. Above that, the allowable current derates stepwise: 38.1 A at 45 °C, 35.59 A at 50 °C, 32.29 A at 55 °C, 28.19 A at 60 °C, 23.3 A at 65 °C, and 17.62 A at 70 °C. That's the standard residential and light-commercial SCCR for a final subcircuit; if your available fault current exceeds 10 kA at the panel, you'll need a current-limiting MCB upstream or a higher-rated RCCB variant. Mounting position is any orientation — no restriction on upright or sideways. Not for wet or washdown environments.","metaTitle":"Siemens SENTRON 5SV3314-6GV01 RCCB, 40A, 2P, Type A, 10 kA","metaDescription":"Siemens 5SV3314-6GV01 SENTRON RCCB, 40 A rated, 230 V AC, 2-pole, Type A, 10 kA short-circuit rating, DIN rail mount. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV3314-6GV01","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","at 40 Cel":"40 A","at 45 Cel":"38.1 A","at 50 Cel":"35.59 A","at 55 Cel":"32.29 A","at 60 Cel":"28.19 A","at 65 Cel":"23.3 A","at 70 Cel":"17.62 A","Rated Value":"50 Hz","description":"Residual current operated circuit breaker, 2-pole, type A, In: 40 A, 30 mA, Un AC: 230 V, Bulk packaging 36 units","Mounting type":"DIN rail (REG)","Number of poles":"2","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Product variations":"Bulk packaging 36 units","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Product designation":"RCCB","Protection class IP":"IP20, if the distribution board is installed, with connected conductors","at AC / rated value":"230 V","Overvoltage category":"III","Design of the product":"Instantaneous","Number of width units":"2","Type of fault current":"A","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","I2t-value / permissible":"58 000 A²·s","circuit-breaker / Design":"5SV3","Short-circuit current rating":"10 kA","Current / at AC / rated value":"40 A","Product feature / silicon-free":"Yes","For Testing Equipment / Minimum":"195 V","Position / of power supply cord":"top or bottom","Protection against electrical shock":"Finger and back-of-hand safe","Surge current resistance / rated value":"1 kA","Switching function / short-term delayed":"No","Tripping residual current / rated value":"30 mA","Size of installation devices / acc. to DIN 43880":"1","Mechanical service life (switching cycles) / typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/31e87024edc705158dabe23aa6cb0947.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=572868&mlfb=5SV3314-6GV01"},"ai":{"faq":[{"question":"What is 5SV3314-6GV01 used for?","answer":"It is a 2-pole RCCB (residual current circuit breaker) used for earth-fault protection in AC final subcircuits up to 40 A, 230 V. Type A detection makes it suitable for circuits with rectifier loads like VFDs, switching power supplies, and LED drivers."},{"question":"What is the temperature derating for 5SV3314-6GV01?","answer":"Rated 40 A at 40 °C ambient. Derates to 38.1 A at 45 °C, 35.59 A at 50 °C, 32.29 A at 55 °C, 28.19 A at 60 °C, 23.3 A at 65 °C, and 17.62 A at 70 °C. In a hot enclosure, size the upstream protection for the derated value."},{"question":"Where can I buy 5SV3314-6GV01?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3314-6GV01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3314-6GV01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}