{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3314-6KK13","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3314-6KK13","canonicalUrl":"https://aoctrl.com/siemens/5SV3314-6KK13","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3314-6KK13","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3314-6KK13 RCCB, 2-pole, Type A, 40 A rated, 30 mA trip, instantaneous, 10 kA SCCR, 50 Hz, DIN rail mount, IP20.","salesMarkdown":"The Siemens SENTRON 5SV3314-6KK13 is a 2-pole residual current circuit breaker (RCCB) rated for 40 A at 50 Hz, with a 30 mA trip threshold and Type A sensitivity — meaning it detects sinusoidal AC fault currents plus pulsating DC residual currents, which covers most modern electronic loads like VFDs, switched-mode supplies, and single-phase rectifiers. Rated short-circuit withstand is 10 kA per the product standard, with an IEC 61008-1 / EN 60898 conditional rating of 0.5 kA — the 10 kA figure governs the upstream backup fuse or MCB coordination; the 0.5 kA is the RCCB's own breaking capacity under those standards. ## Thermal derating — what the 40 A means at panel temperature At 45 °C it derates to 38.1 A, at 50 °C to 35.59 A, at 55 °C to 32.29 A, at 60 °C to 28.19 A, at 65 °C to 23.3 A, and at 70 °C to 17.6 A. If the distribution board runs hot — adjacent high-current breakers, poor ventilation, or a sealed enclosure — the actual continuous current the RCCB can carry drops significantly. Size the upstream load accordingly. Mounting position is any orientation. Rated IP20 once installed in the distribution board with conductors connected — the enclosure provides the environmental seal; this is a panel-internal device, not a standalone outdoor unit.","metaTitle":"Siemens 5SV3314-6KK13 SENTRON RCCB, 40 A, 30 mA, Type A, 2-P","metaDescription":"Siemens SENTRON 5SV3314-6KK13 RCCB, 40 A rated, 30 mA trip, Type A, 2-pole, 10 kA SCCR, IP20. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV3314-6KK13","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, type A, In: 40 A, 30 mA, Un AC: 24-125 V","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"Un AC: 24-125 V","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Operating Frequency":"50 Hz","Product Designation":"RCCB","at AC / rated value":"40 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","I2t value / permissible":"58 000 A²·s","at 40 °C / rated value":"40 A","at 45 °C / rated value":"38.1 A","at 50 °C / rated value":"35.59 A","at 55 °C / rated value":"32.29 A","at 60 °C / rated value":"28.19 A","at 65 °C / rated value":"23.3 A","at 70 °C / rated value":"17.6 A","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Product Feature / Silicon-Free":"Yes","acc. to EN 60898 / rated value":"0.5 kA","For Testing Equipment / Minimum":"24 V","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"5 200 kA","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Current Resistance / Rated Value":"1 kA","according to IEC 61008-1 / rated value":"0.5 kA","Switching Function / Short-Term Delayed":"No","size of installation devices / acc. to DIN 43880":"1","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d557bfe4b8795687259e1d0556707072.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=627685&mlfb=5SV3314-6KK13"},"ai":{"faq":[{"question":"What is the 5SV3314-6KK13 used for?","answer":"It is a 2-pole Type A RCCB rated 40 A / 30 mA for AC residual current and pulsating DC fault protection in 50 Hz circuits, typically in residential or light commercial distribution boards protecting socket outlets, lighting, and small appliance circuits."},{"question":"What are the key ratings of the 5SV3314-6KK13?","answer":"Rated current 40 A, residual trip 30 mA, Type A, 2-pole, 10 kA SCCR, 50 Hz, instantaneous design, overvoltage category III, operating ambient -25 °C to 45 °C, storage -40 °C to 75 °C."},{"question":"Where can I buy the 5SV3314-6KK13?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."},{"question":"What compliance documentation does Siemens provide for the 5SV3314-6KK13?","answer":"The RCCB is designed to IEC 61008-1 and EN 60898 standards, carries overvoltage category III, and is rated IP20 when installed. The manufacturer provides standard compliance documentation including CE declaration and product data sheets."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3314-6KK13","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3314-6KK13 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}