{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3314-6LA01","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3314-6LA01","canonicalUrl":"https://aoctrl.com/siemens/5SV3314-6LA01","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3314-6LA01","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, 2-pole, Type A, short-time delayed, In: 40 A, 30 mA, Un AC: 230 V, with thermal overload protection.","salesMarkdown":"It includes thermal overload protection and is designed for 230 V AC supply at 50/60 Hz. The supply can be connected from top or bottom. IP20 rating applies once the distribution board is installed with conductors connected — standard for enclosed panel use. Silicon-free construction suits environments where silicone contamination must be avoided.","metaTitle":"Siemens SENTRON 5SV3314-6LA01 RCCB, 2-pole, 40 A, 30 mA, Typ","metaDescription":"Siemens SENTRON 5SV3314-6LA01 RCCB, 2-pole, Type A, short-time delayed, 40 A rated current, 30 mA residual current, 230 V AC, 10 kA SCCR. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV3314-6LA01","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, Type A, short-time delayed, In: 40 A, 30 mA, Un AC: 230 V, with thermal overload protection","Grid Spacing":"60 mm","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"With thermal overload protection","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Short-time delayed","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"top or bottom","according to IEC 61008-1 rated value":"0.5 kA","Switching Function Short-Term Delayed":"Yes","Value Range Of The Operating Frequency":"50/60 Hz","value range of the supply voltage at AC":"230 V","Ambient Temperature During Storage Minimum":"-40 °C","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"195 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","Short-Circuit Current Of Series Fuse Maximum Permissible":"80 A","for rated value of the current at AC in hot operating state per pole":"1.5 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c49e3e164fb19dfb4ed1f78a51756cf4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=683210&mlfb=5SV3314-6LA01"},"ai":{"faq":[{"question":"What are the key ratings of the 5SV3314-6LA01?","answer":"It is a 2-pole RCCB, Type A, short-time delayed, rated 40 A with 30 mA residual current, 230 V AC, 10 kA SCCR, and includes thermal overload protection."},{"question":"Where can I buy the 5SV3314-6LA01?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3314-6LA01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3314-6LA01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}