{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3316-6KK01","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3316-6KK01","canonicalUrl":"https://aoctrl.com/siemens/5SV3316-6KK01","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3316-6KK01","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, 2-pole, 63A rated at 40°C, 30mA Type A residual current, short-time delayed, DIN rail mount, 36 mm width.","salesMarkdown":"The Siemens SENTRON 5SV3316-6KK01 is a 2-pole residual current circuit breaker (RCCB) rated 63 A at 40 °C, with a 30 mA Type A residual current trip and short-time delayed characteristic. The short-time delay (selective / S-type) gives it a deliberate trip delay so it coordinates with downstream RCCBs, letting the closer device clear a ground fault first without the upstream one dropping the whole panel. Rated 63 A all the way up to 60 °C ambient (–), then derates to 56.96 A at 65 °C and 48.19 A at 70 °C. That thermal headroom matters if the RCCB lives in a crowded enclosure near transformers or other heat sources — you don't lose capacity until well above typical panel temps. The 30 mA trip threshold is the standard for personal protection against indirect contact in residential and commercial circuits — IEC 60364 says 30 mA RCDs for socket-outlet circuits and final circuits supplying portable equipment. The short-circuit withstand is 10 kA per IEC 61008-1, with an I²t let-through of 110 000 A²·s and a peak let-through current of 7 100 A. That means it coordinates with a 10 kA-rated upstream MCB without needing an extra fuse. Mounting position is any, supply connection top or bottom. The IP20 rating is typical for a DIN-rail device inside a closed distribution board — it's not for wet locations.","metaTitle":"Siemens SENTRON 5SV3316-6KK01 RCCB, 2P, 63A, 30mA Type A","metaDescription":"Siemens SENTRON 5SV3316-6KK01 RCCB, 2-pole, 63A rated, 30mA residual current, Type A, short-time delayed. DIN rail mount. Current-production. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV3316-6KK01","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, type A, short-time delayed, In: 63 A, 30 mA, Un AC: 230 V","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Product Designation":"RCCB","acc. to IEC 81346-2":"F","at AC / rated value":"230 V","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Short-time delayed","Residual Current Type":"A","acc. to DIN EN 61346-2":"F","I2t value / permissible":"110 000 A²·s","at 40 °C / rated value":"63 A","at 45 °C / rated value":"63 A","at 50 °C / rated value":"63 A","at 55 °C / rated value":"63 A","at 60 °C / rated value":"63 A","at 65 °C / rated value":"56.96 A","at 70 °C / rated value":"48.19 A","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Product Feature / Silicon-Free":"Yes","acc. to EN 60898 / rated value":"0.8 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"7 100 kA","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Current Resistance / Rated Value":"3 kA","according to IEC 61008-1 / rated value":"0.8 kA","Switching Function / Short-Term Delayed":"Yes","operational current / at AC / rated value":"63 A","size of installation devices / acc. to DIN 43880":"1","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e0880a072e9da7f86c0fe8a59c98c57a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=604169&mlfb=5SV3316-6KK01"},"ai":{"faq":[{"question":"Where can I buy the 5SV3316-6KK01?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."},{"question":"What are the key ratings of the 5SV3316-6KK01?","answer":"2-pole RCCB, 63 A rated current at 40 °C, 30 mA Type A residual current, short-time delayed, 10 kA short-circuit withstand, 36 mm width (2 MW), DIN rail mount."},{"question":"Will the 5SV3316-6KK01 drop into a panel designed for a 5SU9156-7VK06?","answer":"Both are 2-pole RCCBs on a 36 mm DIN-rail footprint, so the mechanical fit is the same. The 5SV3316-6KK01 is a 63 A Type A short-time delayed device; the 5SU9156-7VK06 is a different rating class. Verify the panel's ampacity and trip coordination before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3316-6KK01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3316-6KK01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}