{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3317-3","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3317-3","canonicalUrl":"https://aoctrl.com/siemens/5SV3317-3","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3317-3","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3 series RCCB, Type F, short-time delayed, 2-pole, 80 A at 40 °C, 230 V AC, 10 kA SCCR, DIN rail mount.","salesMarkdown":"The short-time delayed switching function (marked as short-time delayed in the design) gives it selectivity against transient nuisance trips — it holds through brief inrush or surge events that would trip a standard instantaneous RCCB. The current derating curve is the real selection gate here: 80 A at 40 °C drops to 77.87 A at 45 °C, 74.77 A at 50 °C, 70.26 A at 55 °C, 64.32 A at 60 °C, 56.96 A at 65 °C, and 48.19 A at 70 °C. The 10 kA SCCR at 230 V AC means it's rated for installation at the service entrance or sub-distribution board where available fault current is moderate; for higher fault levels you'd need a current-limiting upstream breaker. The 70 mm installation depth and 36 mm width (2 width units) mean it occupies the same slot as a standard 2-pole MCB, so it drops into an existing distribution board without re-spacing. Conductor cross-section accepts 0.75 to 35 mm² solid or stranded — that covers everything from control wiring (1.5 mm²) up to a 35 mm² feeder tail. Supply connection can be top or bottom, which simplifies busbar routing in a crowded panel. The Type F fault current classification is per IEC/EN 62423, covering circuits with variable-speed drives, washing machines, and other electronics that generate mixed-frequency leakage. The short-time delayed characteristic (3 kA surge current resistance, 110 000 A²·s I²t withstand) gives coordination with surge protective devices and selectivity with downstream RCCBs. Silicon-free construction is specified, which matters for applications where silicone outgassing can contaminate contacts or optics.","metaTitle":"Siemens 5SV3317-3 SENTRON RCCB Type F, 80 A, 2-pole, 10 kA","metaDescription":"Siemens 5SV3317-3 SENTRON RCCB, Type F fault current, 80 A rated at 40°C, 2-pole, 10 kA SCCR, 230 V AC. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Solid":"0.75 ... 35 mm²","Width":"36 mm","Height":"90 mm","Stranded":"0.75 ... 35 mm²","at 40 Cel":"80 A","at 45 Cel":"77.87 A","at 50 Cel":"74.77 A","at 55 Cel":"70.26 A","at 60 Cel":"64.32 A","at 65 Cel":"56.96 A","at 70 Cel":"48.19 A","Rated Value":"50 Hz","Mounting type":"DIN rail (REG)","During Storage":"-40 ... +75 °C","Number of poles":"2","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Ambient temperature":"-25 ... +45 °C","Operating frequency":"50/60Hz","Product designation":"RCCB","Protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage category":"III","Design of the product":"Short-time delayed","Number of width units":"2","Type of fault current":"F","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","I2t-value / permissible":"110 000 A²·s","circuit-breaker / Design":"5SV3","Short-circuit current rating":"10 kA","Current / at AC / rated value":"80 A","Product feature / silicon-free":"Yes","Position / of power supply cord":"top or bottom","Protection against electrical shock":"Finger and back-of-hand safe","Supply voltage / at AC / rated value":"230 V","Surge current resistance / rated value":"3 kA","Switching function / short-term delayed":"Yes","Tripping residual current / rated value":"30 mA","Tightening torque / with screw-type terminals":"2.5 ... 3 N·m","Size of installation devices / acc. to DIN 43880":"1","Supply voltage / for testing equipment / minimum":"195 V","Mechanical service life (switching cycles) / typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=604170&mlfb=5SV3317-3","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV3317-3/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SV3317-3 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 5SV3317-3's listed depth?","answer":"The listed depth is 70 mm, with an installation depth of 70 mm — it clears most standard distribution board enclosures."},{"question":"What conductor sizes does 5SV3317-3 accept?","answer":"It accepts 0.75 to 35 mm² solid or stranded conductors, covering control wiring up to feeder tails."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3317-3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3317-3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}