{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3317-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3317-6","canonicalUrl":"https://aoctrl.com/siemens/5SV3317-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3317-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3317-6 RCCB, 80 A, 30 mA, Type A, 2-pole, instantaneous, DIN rail mount, 50 Hz.","salesMarkdown":"Instantaneous response — no intentional short-time delay — so it clears fast on a ground fault. Feed from top or bottom; mounting position any orientation. Derate linearly above 40 °C: 77.87 A at 45 °C, 74.77 A at 50 °C, 70.26 A at 55 °C, 64.32 A at 60 °C, 56.96 A at 65 °C, 48.2 A at 70 °C. If the distribution board runs hot, the 5SV3317-6 still carries load but the headroom shrinks. The short-circuit current rating (SCCR) is 10 kA per IEC 61008-1 and 0.8 kA per EN 60898 — the 10 kA figure governs the fault-clearing capability at the RCCB's terminals; the 0.8 kA is the conditional rating when backed by an upstream overcurrent device. Surge current resistance rated 1 kA, I²t let-through 110 000 A²s. Type A residual current detection covers sinusoidal AC and pulsed DC faults up to 30 mA — standard for circuits with rectified loads (washing machines, LED drivers, EV chargers). The 70 mm installation depth matches standard distribution board enclosures; no extra clearance needed behind the rail. IP20 with connected conductors in an installed distribution board — not rated for wet or dusty environments. Overvoltage category III, suitable for fixed-installation downstream of the service entrance. Silicon-free construction, which matters for potting or conformal-coating processes in sensitive electronics panels.","metaTitle":"Siemens 5SV3317-6 SENTRON RCCB, 80 A, 30 mA, Type A, 2-pole","metaDescription":"Siemens 5SV3317-6 SENTRON RCCB, 80 A rated, 30 mA trip, Type A, 2-pole, instantaneous, DIN rail mount. Available to order; confirm current pricing via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Operating Frequency":"50 Hz","Product Designation":"RCCB","at AC / rated value":"80 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","I2t value / permissible":"110 000 A²·s","at 40 °C / rated value":"80 A","at 45 °C / rated value":"77.87 A","at 50 °C / rated value":"74.77 A","at 55 °C / rated value":"70.26 A","at 60 °C / rated value":"64.32 A","at 65 °C / rated value":"56.96 A","at 70 °C / rated value":"48.2 A","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Product Feature / Silicon-Free":"Yes","acc. to EN 60898 / rated value":"0.8 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"7 100 kA","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Current Resistance / Rated Value":"1 kA","according to IEC 61008-1 / rated value":"0.8 kA","Switching Function / Short-Term Delayed":"No","size of installation devices / acc. to DIN 43880":"1","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/32b1702b5f33fc850c1a2e335b5b05f8.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=143168&mlfb=5SV3317-6","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV3317-6/alternatives.json"},"ai":{"faq":[{"question":"What is the 5SV3317-6's depth?","answer":"70 mm depth, which is also the installation depth — it fits standard 70 mm deep distribution board cutouts without protruding past the DIN rail."},{"question":"What is the 5SV3317-6's width?","answer":"36 mm, which corresponds to 2 modular width units on a DIN rail. That's a standard 2-pole RCCB footprint."},{"question":"Where can I buy the 5SV3317-6 and get current pricing?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3317-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3317-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}