{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3317-6KL","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3317-6KL","canonicalUrl":"https://aoctrl.com/siemens/5SV3317-6KL","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3317-6KL","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3317-6KL, RCCB, 2-pole, 80 A rated, 30 mA residual, Type A, instantaneous, DIN rail, IP20.","salesMarkdown":"## RCCB for 50 Hz distribution boards The Siemens 5SV3317-6KL is a 2-pole residual-current circuit breaker (RCCB) from the SENTRON family, rated 80 A at 40 °C with a 30 mA trip threshold and Type A waveform sensitivity. It is an instantaneous (short-time-delay) device, meaning it trips without intentional delay on a residual fault — suited for general-purpose shock protection in 50 Hz TN and TT systems. ## SCCR and fault coordination The device carries a short-circuit current rating (SCCR) of 10 kA per IEC 61008-1, with a conditional rated short-circuit current of 0.8 kA when backed by an upstream overcurrent device per EN 60898. The let-through energy I²t is rated at 110 000 A²·s, and the surge-current withstand is 1 kA (8/20 µs waveform). These figures govern coordination with the upstream MCB or fuse — the 0.8 kA conditional rating means the RCCB relies on the backup protection to clear a fault above that level without damage to the device. Depth is 70 mm, which matches the standard SENTRON RCCB profile — no extra panel depth required beyond the usual 70 mm for the distribution board. The N terminal is on the left side of the 2-pole block. Silicon-free construction is specified, relevant for potting or conformal-coating processes in sensitive environments. Derate linearly: 77.87 A at 45 °C, 74.77 A at 50 °C, 70.26 A at 55 °C, 64.32 A at 60 °C, 56.96 A at 65 °C, and 48.2 A at 70 °C. Overvoltage category III (distribution-board level).","metaTitle":"Siemens 5SV3317-6KL SENTRON RCCB, 80A 30mA Type A, 2-Pole","metaDescription":"Siemens SENTRON 5SV3317-6KL RCCB, 80A rated, 30mA trip, Type A, 2-pole, instantaneous. Current production. DIN rail mount. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"N left","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Operating Frequency":"50 Hz","Product Designation":"RCCB","at AC / rated value":"80 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","I2t value / permissible":"110 000 A²·s","at 40 °C / rated value":"80 A","at 45 °C / rated value":"77.87 A","at 50 °C / rated value":"74.77 A","at 55 °C / rated value":"70.26 A","at 60 °C / rated value":"64.32 A","at 65 °C / rated value":"56.96 A","at 70 °C / rated value":"48.2 A","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Product Feature / Silicon-Free":"Yes","acc. to EN 60898 / rated value":"0.8 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"7 100 kA","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Current Resistance / Rated Value":"1 kA","according to IEC 61008-1 / rated value":"0.8 kA","Switching Function / Short-Term Delayed":"No","size of installation devices / acc. to DIN 43880":"1","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/353ca88e59dfbe900cfd4de25dbc0441.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=91747&mlfb=5SV3317-6KL","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV3317-6KL/alternatives.json"},"ai":{"faq":[{"question":"What is 5SV3317-6KL's depth and width for panel layout?","answer":"Depth is 70 mm, width is 36 mm (2 modular width units on DIN rail). This matches the standard SENTRON RCCB footprint."},{"question":"What compliance documentation does Siemens provide for 5SV3317-6KL?","answer":"The device is designed to IEC 61008-1 and EN 60898, carries overvoltage category III, and is rated IP20 in an installed distribution board. Silicon-free construction is noted. RoHS, REACH, and CE declarations are standard for the SENTRON series."},{"question":"Where can I buy 5SV3317-6KL and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock or price figures are published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3317-6KL","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3317-6KL when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}