{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3347-3","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3347-3","canonicalUrl":"https://aoctrl.com/siemens/5SV3347-3","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3347-3","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, 4-pole, 80 A rated, 30 mA trip, Type F, short-time delayed, 10 kA SCCR, DIN rail mount, IP20.","salesMarkdown":"It's short-time delayed (selective), so it coordinates downstream with standard RCCBs to keep only the faulted branch off the bus. Mounting position any orientation. Supply feeds top or bottom. IP20 with conductors connected inside a distribution board — standard for enclosed panel use, not outdoor or washdown. At 45 °C it derates to 77.57 A; at 50 °C to 74.59 A; at 55 °C to 70.22 A; at 60 °C to 64.47 A; at 65 °C to 57.35 A; at 70 °C to 48.8 A.","metaTitle":"Siemens 5SV3347-3 SENTRON RCCB, 4P, 80A, 30mA, Type F, 10kA","metaDescription":"Siemens 5SV3347-3 SENTRON RCCB, 4-pole, 80A rated, 30mA trip, Type F, 10kA SCCR, short-time delayed. DIN rail mount. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"72 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Number Of Poles":"4","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Product Designation":"RCCB","at AC / rated value":"80 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Short-time delayed","Residual Current Type":"F","I2t value / permissible":"110 000 A²·s","at 40 °C / rated value":"80 A","at 45 °C / rated value":"77.57 A","at 50 °C / rated value":"74.59 A","at 55 °C / rated value":"70.22 A","at 60 °C / rated value":"64.47 A","at 65 °C / rated value":"57.35 A","at 70 °C / rated value":"48.8 A","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"4","Product Feature / Silicon-Free":"Yes","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"7 100 A","Tripping Fault Current / Rated Value":"30 mA","Surge Current Resistance / Rated Value":"3 kA","according to IEC 61008-1 / rated value":"0.8 kA","Switching Function / Short-Term Delayed":"Yes","Value Range / Of The Operating Frequency":"50/60 Hz","value range / of the supply voltage / at AC":"400 V","Value Range / Of The Supply Voltage Frequency":"50 Hz","Supply Voltage / For Testing Equipment / Minimum":"195 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2f9e83eb169179ddd4428d6075f216bf.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=604178&mlfb=5SV3347-3","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV3347-3/alternatives.json"},"ai":{"faq":[{"question":"What is 5SV3347-3's listed depth?","answer":"70 mm."},{"question":"What is 5SV3347-3's listed width?","answer":"72 mm (4 modular width units)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3347-3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3347-3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}