{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3347-6KK01","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3347-6KK01","canonicalUrl":"https://aoctrl.com/siemens/5SV3347-6KK01","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3347-6KK01","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3347-6KK01, 4-pole type A RCCB, short-time delayed, In 80 A, IΔn 30 mA, Un AC 400 V, 10 kA SCCR, 4 MW, DIN rail.","salesMarkdown":"The Siemens SENTRON 5SV3347-6KK01 is a 4-pole residual current circuit breaker (RCCB), type A, short-time delayed, rated 80 A with a 30 mA trip threshold and 400 V AC supply voltage. The short-time delay (type S / selective characteristic) means it coordinates with downstream RCCBs — it holds during a brief earth fault on a sub-circuit, letting the downstream device clear first, so only the faulted branch is lost. That selectivity matters in distribution boards feeding multiple sub-panels or critical loads where a nuisance trip on the incomer takes everything dark. Mounting position is unrestricted. Silicon-free construction suits environments where silicone outgassing can contaminate contacts or optics. Rated short-circuit current withstand is 10 kA, and the conditional short-circuit rating per IEC 61008-1 is 0.8 kA. The maximum permissible series fuse short-circuit current is 100 A — relevant when the RCCB is backed by a larger upstream fuse.","metaTitle":"Siemens 5SV3347-6KK01 SENTRON RCCB, 4-pole, 80 A, 30 mA, 400","metaDescription":"Siemens SENTRON 5SV3347-6KK01 RCCB, 4-pole type A, short-time delayed, 80 A, 30 mA, 400 V AC, 10 kA SCCR, DIN rail. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"72 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Grid Spacing":"60 mm","Number Of Poles":"4","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Short-time delayed","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"4","Position Of Power Supply Cord":"top or bottom","according to IEC 61008-1 rated value":"0.8 kA","Switching Function Short-Term Delayed":"Yes","Value Range Of The Operating Frequency":"50/60 Hz","value range of the supply voltage at AC":"400 V","Ambient Temperature During Storage Minimum":"-40 °C","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"195 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","Short-Circuit Current Of Series Fuse Maximum Permissible":"100 A","for rated value of the current at AC in hot operating state per pole":"4.1 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2f9e83eb169179ddd4428d6075f216bf.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=604179&mlfb=5SV3347-6KK01","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV3347-6KK01/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 5SV3347-6KK01?","answer":"The 5SV3347-6KK01 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Will the 5SV3347-6KK01 drop into a panel specified around the 5SL4363-7?","answer":"No — the 5SL4363-7 is a 3-pole miniature circuit breaker (MCB), not an RCCB, and occupies 3 MW (54 mm wide) versus the 5SV3347-6KK01's 4 MW (72 mm). The function, pole count, and width differ, so a direct drop-in without rewiring and panel modification is not possible."},{"question":"What compliance documentation does Siemens provide for the 5SV3347-6KK01?","answer":"The 5SV3347-6KK01 is designed according to IEC 61008-1 and carries overvoltage category III. Standard Siemens documentation includes a CE declaration of conformity and RoHS/REACH compliance data — available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3347-6KK01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3347-6KK01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}