{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3412-6KL","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3412-6KL","canonicalUrl":"https://aoctrl.com/siemens/5SV3412-6KL","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3412-6KL","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3 series RCCB, 2-pole, 25 A, Type A, 230/400 V AC, 10 kA short-circuit rating, instantaneous, DIN rail mount, 36 mm wide.","salesMarkdown":"## What this RCCB does on the line The Siemens 5SV3412-6KL is a 2-pole residual current circuit breaker (RCCB) from the SENTRON 5SV3 series, rated 25 A at 230/400 V AC, 50 Hz, with a Type A fault-current characteristic. Rated current holds at 25 A from 40 °C through 60 °C ambient; above that, derate to 23.3 A at 65 °C and 17.62 A at 70 °C — a factor to check if the RCCB lives in a hot enclosure. Supply can land top or bottom; mounting position is unrestricted. IP20 with conductors connected and distribution board installed — fine for enclosed panels, not for washdown zones. Overvoltage category III suits fixed-installation distribution boards.","metaTitle":"Siemens 5SV3412-6KL SENTRON RCCB, 25 A, 2-pole, Type A, 10 k","metaDescription":"Siemens 5SV3412-6KL SENTRON RCCB, 25 A, 2-pole, Type A, 10 kA short-circuit rating. 36 mm wide, DIN rail mount. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Solid":"0.75 ... 35 mm²","Width":"36 mm","Height":"90 mm","Stranded":"0.75 ... 35 mm²","at 40 Cel":"25 A","at 45 Cel":"25 A","at 50 Cel":"25 A","at 55 Cel":"25 A","at 60 Cel":"25 A","at 65 Cel":"23.3 A","at 70 Cel":"17.62 A","Rated Value":"50 Hz","Mounting type":"DIN rail (REG)","During Storage":"-40 ... +75 °C","Number of poles":"2","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Product variations":"N left","Ambient temperature":"-25 ... +45 °C","Product designation":"RCCB","Protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage category":"III","Design of the product":"Instantaneous","Number of width units":"2","Type of fault current":"A","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","I2t-value / permissible":"58 000 A²·s","circuit-breaker / Design":"5SV3","Short-circuit current rating":"10 kA","Current / at AC / rated value":"25 A","Product feature / silicon-free":"Yes","Position / of power supply cord":"top or bottom","Protection against electrical shock":"Finger and back-of-hand safe","Supply voltage / at AC / rated value":"230/400 V","Surge current resistance / rated value":"1 kA","Switching function / short-term delayed":"No","Tripping residual current / rated value":"100 mA","Tightening torque / with screw-type terminals":"2.5 ... 3 N·m","Size of installation devices / acc. to DIN 43880":"1","Supply voltage / for testing equipment / minimum":"100 V","Mechanical service life (switching cycles) / typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0c10548c2a77f7b785c1f47b48e79825.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=372986&mlfb=5SV3412-6KL","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV3412-6KL/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 5SV3412-6KL?","answer":"The depth is 70 mm, matching the installation depth."},{"question":"What wire sizes does 5SV3412-6KL accept?","answer":"Solid or stranded copper from 0.75 mm² up to 35 mm²."},{"question":"Where can I buy 5SV3412-6KL and how is it quoted?","answer":"Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Will 5SV3412-6KL drop into a panel specified around 5SL6563-7BB without rewiring?","answer":"Both are 2-pole RCCBs on DIN rail, but 5SL6563-7BB is a different series (5SL vs 5SV3) with different dimensions and ratings — verify the panel cutout and wiring before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3412-6KL","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3412-6KL when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}