{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3414-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3414-6","canonicalUrl":"https://aoctrl.com/siemens/5SV3414-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3414-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, 5SV3414-6, 40 A, 100 mA, Type A, 2-pole, 10 kA, 50 Hz, IP20.","salesMarkdown":"The Siemens SENTRON 5SV3414-6 is a 2-pole residual current circuit breaker (RCCB) rated for 40 A at 50 Hz, with a 100 mA trip threshold and Type A sensitivity. It handles a 10 kA short-circuit current rating and fits a standard 2-module DIN-rail footprint (36 mm wide). The 40 A rating holds at 40 °C ambient; at 45 °C it derates to 38.1 A, and at 60 °C it drops to 28.19 A. If your panel runs warm, size the upstream breaker accordingly — the 40 A nameplate is only valid at 40 °C. Type A detection covers pulsating DC residual currents up to 100 mA, which is the standard for single-phase electronics and variable-speed drives. The instantaneous design means no intentional delay — it trips within the RCD curve, not the S-curve. Not a daily-switch application. Snaps onto DIN rail (REG), any mounting position. Depth is 70 mm, width 36 mm (2 MW), height 90 mm. IP20 with the distribution board installed and conductors connected.","metaTitle":"Siemens SENTRON 5SV3414-6 RCCB, 40 A, 100 mA, Type A, 2-Pole","metaDescription":"Siemens SENTRON 5SV3414-6 residual current circuit breaker (RCCB), 40 A rated, 100 mA trip, Type A, 2-pole, 10 kA SCCR, 50 Hz, IP20. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV3414-6","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, type A, In: 40 A, 100 mA, Un AC: 230 V","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Operating Frequency":"50 Hz","Product Designation":"RCCB","at AC / rated value":"40 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","I2t value / permissible":"58 000 A²·s","at 40 °C / rated value":"40 A","at 45 °C / rated value":"38.1 A","at 50 °C / rated value":"35.59 A","at 55 °C / rated value":"32.29 A","at 60 °C / rated value":"28.19 A","at 65 °C / rated value":"23.3 A","at 70 °C / rated value":"17.6 A","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Product Feature / Silicon-Free":"Yes","For Testing Equipment / Minimum":"100 V","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"5 200 A","Tripping Fault Current / Rated Value":"100 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Current Resistance / Rated Value":"1 kA","according to IEC 61008-1 / rated value":"0.5 kA","Switching Function / Short-Term Delayed":"No","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$124.14","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3a10d0f7343516da5b571ddb06a91a97.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=392722&mlfb=5SV3414-6"},"ai":{"faq":[{"question":"What is the depth of the 5SV3414-6?","answer":"70 mm."},{"question":"What is the width of the 5SV3414-6?","answer":"36 mm (2 modular width units)."},{"question":"Will 5SV3414-6 drop into a panel specified around 5SL4363-7 without rewiring?","answer":"No. The 5SL4363-7 is an MCB; the 5SV3414-6 is an RCCB. They occupy the same DIN-rail footprint (2 MW), but the wiring and protection function are different — you cannot simply swap one for the other."},{"question":"What compliance documentation does Siemens provide for 5SV3414-6?","answer":"The part is designed to IEC 61008-1. Silicon-free construction is declared. RoHS/REACH status is standard for Siemens SENTRON products but is not detailed in this listing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3414-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3414-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}