{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3416-6KL","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3416-6KL","canonicalUrl":"https://aoctrl.com/siemens/5SV3416-6KL","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3416-6KL","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3416-6KL, 2-pole RCCB, 63 A, 100 mA Type A, 10 kA, 50 Hz, DIN rail, IP20.","salesMarkdown":"## RCCB for 50 Hz panels — 63 A, 100 mA Type A, 10 kA SCCR The Siemens 5SV3416-6KL is a 2-pole SENTRON RCCB rated 63 A with a 100 mA Type A trip characteristic, designed for 50 Hz installations. Type A detection catches pulsating DC residual currents from single-phase rectified loads. Snaps onto standard DIN rail (REG per) in any mounting position. Supply feeds top or bottom — no polarity constraint. IP20 rating applies only when the distribution board is installed with connected conductors; the body itself is not sealed against washdown. Silicon-free construction suits environments where outgassing must be avoided, such as sealed enclosures near sensitive optics or coating lines. Rated 63 A continuously from 40 °C through 55 °C ambient. At 65 °C it derates to 56.96 A; at 70 °C to 48.2 A. Storage range is -40 to +75 °C, operating range -25 to +45 °C. The 1 kA surge current resistance and 110 000 A²s I²t withstand cover inrush from downstream loads without nuisance tripping. Current production. No LTB or EOL notice.","metaTitle":"Siemens 5SV3416-6KL SENTRON RCCB, 2-pole, 63 A, 100 mA, Type","metaDescription":"Siemens 5SV3416-6KL SENTRON 2-pole RCCB, 63 A rated, 100 mA Type A residual current, 10 kA SCCR, 50 Hz, DIN rail. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV3416-6KL","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, type A, In: 63 A, 100 mA, Un AC: 230 V, N left","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"N left","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Operating Frequency":"50 Hz","Product Designation":"RCCB","at AC / rated value":"63 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","I2t value / permissible":"110 000 A²·s","at 40 °C / rated value":"63 A","at 45 °C / rated value":"63 A","at 50 °C / rated value":"63 A","at 55 °C / rated value":"63 A","at 60 °C / rated value":"63 A","at 65 °C / rated value":"56.96 A","at 70 °C / rated value":"48.2 A","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Product Feature / Silicon-Free":"Yes","acc. to EN 60898 / rated value":"0.8 kA","For Testing Equipment / Minimum":"100 V","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"7 100 kA","Tripping Fault Current / Rated Value":"100 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Current Resistance / Rated Value":"1 kA","according to IEC 61008-1 / rated value":"0.8 kA","Switching Function / Short-Term Delayed":"No","size of installation devices / acc. to DIN 43880":"1","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8a054719cc83567bb6080c11be06c8ad.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=267631&mlfb=5SV3416-6KL"},"ai":{"faq":[{"question":"What is the closest functional second-source to 5SV3416-6KL?","answer":"The 5SU9354-7KK16 is a peer RCCB in the same SENTRON family. Verify your panel's rated current, trip sensitivity, and pole count against that order code before substituting — the 5SV3416-6KL is a 2-pole, 63 A, 100 mA Type A device at 50 Hz."},{"question":"Will 5SV3416-6KL drop into a panel specified around 5SU9354-7KK16 without rewiring?","answer":"Both are DIN-rail RCCBs in the SENTRON family, but the 5SV3416-6KL is a 2-pole, 63 A, 100 mA Type A unit. Confirm the existing panel's rated current, pole count, and trip sensitivity match before direct swap — do not assume identical footprint or wiring without checking the nameplate."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3416-6KL","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3416-6KL when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}