{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3417-6KL","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3417-6KL","canonicalUrl":"https://aoctrl.com/siemens/5SV3417-6KL","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3417-6KL","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3 series, RCCB, 2-pole, Type A, 80 A at 40 °C, 230/400 V AC, 10 kA, DIN rail mount, instantaneous.","salesMarkdown":"## RCCB for the panel — 80 A Type A, instantaneous trip The Siemens 5SV3417-6KL is a 2-pole residual current circuit breaker (RCCB) from the SENTRON 5SV3 series, rated 80 A at 40 °C on a 230/400 V AC supply. Type A fault-current detection means it catches both sinusoidal AC and pulsating DC residual currents — the standard choice for circuits with single-phase rectifiers, switched-mode supplies, or variable-speed drives downstream. Instantaneous trip, no intentional delay, so it clears ground faults fast on circuits where selectivity isn't required. Rated short-circuit withstand is 10 kA (per IEC 61008), and the I²t let-through is 110 000 A²s — enough to coordinate with a 10 kA upstream MCB without the RCCB rupturing on a bolted fault. Surge-current resistance is 1 kA, so it won't nuisance-trip on capacitor inrush or a nearby lightning surge. Mounts on DIN rail (REG profile), occupies 2 width units (36 mm), and accepts conductors from 0.75 to 35 mm² solid or stranded — covers the full range from control wiring up to the incoming tails. ## Thermal derating — what 80 A means in a hot panel Inside a crowded enclosure or near a curing press, ambient climbs. At 45 °C the continuous current drops to 77.87 A; at 50 °C it's 74.77 A; at 55 °C it's 70.26 A; at 60 °C it's 64.32 A; at 65 °C it's 56.96 A; at 70 °C it's 48.19 A. If the panel ambient runs 55 °C, size the load at 70 A max or step up to the next frame. The storage range is -40 to +75 °C — the device can sit in a hot warehouse or cold truck without damage. ## Integration — DIN rail, IP20, any position Mounting position is unrestricted — horizontal, vertical, or upside-down — which helps in tight gland-plate layouts. The IP20 rating applies only when the distribution board is installed with conductors connected; the device itself is finger- and back-of-hand safe per the touch-safe terminals.","metaTitle":"Siemens 5SV3417-6KL SENTRON RCCB, 80 A, 2-pole, Type A, 10 k","metaDescription":"Siemens 5SV3417-6KL SENTRON RCCB, 80 A rated at 40 °C, 2-pole, Type A, 10 kA SCCR. Current lifecycle. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"70 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Mounting":"DIN rail (REG)","Product Status":"Active","Temp Operating Max":"45 °C","Temp Operating Min":"-25 °C","Short Circuit Rating":"10 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f86c74c83a42fecce44a96d185894067.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=214831&mlfb=5SV3417-6KL","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV3417-6KL/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3417-6KL","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3417-6KL when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}