{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3612-3","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3612-3","canonicalUrl":"https://aoctrl.com/siemens/5SV3612-3","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3612-3","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3612-3, Type F RCCB, 2-pole, 25 A rated, 10 kA SCCR, short-time delayed, DIN rail mount, 36 mm wide.","salesMarkdown":"The Siemens SENTRON 5SV3612-3 is a 2-pole residual current circuit breaker (RCCB) rated for 25 A at 230/400 V AC, 50/60 Hz. It detects Type F fault currents — the waveform that covers standard sinusoidal AC plus mixed-frequency residual currents from variable-speed drives and power electronics. That makes it the right choice for circuits feeding VFDs, UPS systems, or any load where the fault signature isn't a clean 50 Hz sine wave. Surge current resistance is 3 kA, and the I²t withstand is 58 000 A²·s, which tells you the device handles high-energy let-through without welding its contacts. The short-time delayed design (Type F with intentional delay) means it rides through brief inrush or transient leakage that would nuisance-trip a standard instantaneous RCCB. That's useful on circuits with capacitive input filters or soft-starters that generate a short pulse of leakage at power-up. Snaps onto a DIN rail (REG profile), occupies 2 width units (36 mm), and accepts conductors from 0.75 mm² up to 35 mm² solid or stranded. Finger and back-of-hand safe protection against accidental contact with live terminals.","metaTitle":"Siemens SENTRON 5SV3612-3 RCCB, Type F, 25 A, 2-pole","metaDescription":"Siemens SENTRON 5SV3612-3 RCCB, Type F, 25 A, 2-pole, 10 kA SCCR, short-time delayed, DIN rail. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Solid":"0.75 ... 35 mm²","Width":"36 mm","title":"5SV3612-3","Height":"90 mm","Stranded":"0.75 ... 35 mm²","at 40 Cel":"25 A","at 45 Cel":"25 A","at 50 Cel":"25 A","at 55 Cel":"25 A","at 60 Cel":"25 A","at 65 Cel":"25 A","at 70 Cel":"25 A","Rated Value":"50 Hz","description":"Residual current operated circuit breaker, 2-pole, type F, short-time delayed, In: 25 A, 300 mA, Un AC: 230 V","Mounting type":"DIN rail (REG)","During Storage":"-40 ... +75 °C","Number of poles":"2","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Ambient temperature":"-25 ... +45 °C","Operating frequency":"50/60Hz","Product designation":"RCCB","Protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage category":"III","Design of the product":"Short-time delayed","Number of width units":"2","Type of fault current":"F","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","I2t-value / permissible":"58 000 A²·s","circuit-breaker / Design":"5SV3","Short-circuit current rating":"10 kA","Current / at AC / rated value":"25 A","Product feature / silicon-free":"Yes","Position / of power supply cord":"top or bottom","Protection against electrical shock":"Finger and back-of-hand safe","Supply voltage / at AC / rated value":"230/400 V","Surge current resistance / rated value":"3 kA","Switching function / short-term delayed":"Yes","Tripping residual current / rated value":"300 mA","Tightening torque / with screw-type terminals":"2.5 ... 3 N·m","Size of installation devices / acc. to DIN 43880":"1","Supply voltage / for testing equipment / minimum":"100 V","Mechanical service life (switching cycles) / typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c6b85cd2aca50122757aac531c5c8bbe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=604183&mlfb=5SV3612-3"},"ai":{"faq":[{"question":"Who supplies 5SV3612-3 and how is it quoted for volume purchases?","answer":"The 5SV3612-3 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is 5SV3612-3's listed depth?","answer":"The 5SV3612-3 has a depth of 70 mm, which fits standard 100 mm deep enclosures with wiring clearance behind the DIN rail."},{"question":"What conductor sizes does 5SV3612-3 accept?","answer":"It accepts solid and stranded conductors from 0.75 mm² up to 35 mm²."},{"question":"What compliance documentation does Siemens provide for 5SV3612-3?","answer":"The 5SV3612-3 carries overvoltage category III rating and is designed for Type F fault current detection per IEC/EN standards. It is silicon-free. Standard Siemens declarations for RoHS and REACH are available upon request through the RFQ process."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3612-3","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3612-3 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}