{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3612-6KK01","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3612-6KK01","canonicalUrl":"https://aoctrl.com/siemens/5SV3612-6KK01","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3612-6KK01","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, 25 A, 300 mA, Type A, short-time delayed, 2-pole, 10 kA SCCR, 230/400 V AC, 50/60 Hz, DIN rail mount, IP20.","salesMarkdown":"It is short-time delayed (short-term delayed per the design), meaning it tolerates brief surge currents up to 3 kA without nuisance tripping — useful on circuits with motor inrush or capacitor banks. The 10 kA short-circuit current rating (SCCR) at 230/400 V AC, 50/60 Hz means it safely interrupts fault currents up to that level without cascading upstream. Type A detection covers sinusoidal AC and pulsating DC residual currents, which is the standard requirement for most modern electronic loads like VFDs, switching power supplies, and LED drivers. Snaps onto standard DIN rail (REG per the spec). Depth is 70 mm, height 90 mm. Mounting position is any orientation, so it fits vertical or horizontal busbar layouts. ## Thermal performance and derating The I²t let-through is 58,000 A²·s, with a peak let-through current of 5,200 A. Silicon-free construction, which matters for certain coating and potting processes in sensitive electronics environments.","metaTitle":"Siemens 5SV3612-6KK01 SENTRON RCCB, 25 A, 300 mA, 2-Pole, Sh","metaDescription":"Siemens 5SV3612-6KK01 SENTRON RCCB, 25 A rated, 300 mA Type A residual current, 10 kA SCCR, short-time delayed, 2-pole, DIN rail mount. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV3612-6KK01","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, type A, short-time delayed, In: 25 A, 300 mA, Un AC: 230 V","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Product Designation":"RCCB","at AC / rated value":"25 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Short-time delayed","Residual Current Type":"A","I2t value / permissible":"58 000 A²·s","at 40 °C / rated value":"25 A","at 45 °C / rated value":"25 A","at 50 °C / rated value":"25 A","at 55 °C / rated value":"25 A","at 60 °C / rated value":"25 A","at 65 °C / rated value":"25 A","at 70 °C / rated value":"25 A","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Product Feature / Silicon-Free":"Yes","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"5 200 A","Tripping Fault Current / Rated Value":"300 mA","Surge Current Resistance / Rated Value":"3 kA","according to IEC 61008-1 / rated value":"0.5 kA","Switching Function / Short-Term Delayed":"Yes","Value Range / Of The Operating Frequency":"50/60 Hz","value range / of the supply voltage / at AC":"230/400 V","Value Range / Of The Supply Voltage Frequency":"50 Hz","Supply Voltage / For Testing Equipment / Minimum":"100 V","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ec2d16c416ea1a05856f773516be1616.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=604184&mlfb=5SV3612-6KK01"},"ai":{"faq":[{"question":"Where can I buy 5SV3612-6KK01 and how do I get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm number."},{"question":"What is 5SV3612-6KK01's listed depth (70 mm) on this component line?","answer":"The listed depth is 70 mm. That is the installed depth on the DIN rail, not including any front projection for the handle or terminals."},{"question":"What is 5SV3612-6KK01's listed width (36 mm) on this component line?","answer":"The width is 36 mm, which corresponds to 2 modular width units on a standard DIN-rail panel. This is a 2-pole device in a compact footprint."},{"question":"What compliance documentation does this brand provide for 5SV3612-6KK01 (RoHS, REACH, UL, IEC)?","answer":"The part is designed per IEC 61008-1 (the RCCB standard) with a rated conditional short-circuit current of 0.5 kA under that standard. The SENTRON series typically carries CE marking for the European market. For specific RoHS/REACH declarations or UL listing, request the manufacturer's declaration at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3612-6KK01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3612-6KK01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}