{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3614-6KL","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3614-6KL","canonicalUrl":"https://aoctrl.com/siemens/5SV3614-6KL","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3614-6KL","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3614-6KL, RCCB, 2-pole, 40 A, 300 mA, Type A, instantaneous, 50 Hz, DIN rail mount.","salesMarkdown":"It is a Type A, instantaneous design — no intentional delay, so it clears ground faults as fast as the waveform allows. Two poles, 50 Hz only, DIN rail mount, 2 MW wide (36 mm). Above that, the part derates linearly: 38.1 A at 45 °C, 35.59 A at 50 °C, down to 17.6 A at 70 °C. If your panel runs hot, check the thermal curve — at 60 °C you only get 28.19 A continuous. The 300 mA sensitivity is standard for general-purpose socket circuits and lighting in commercial or industrial distribution boards; it avoids nuisance tripping from normal leakage in long cable runs. Short-circuit current rating is 10 kA per IEC 61008-1 and 0.5 kA per EN 60898 — the lower EN value governs when the RCCB is used as a standalone device without upstream overcurrent protection coordination. Surge current resistance is 1 kA (8/20 µs), letting it withstand lightning-induced transients without false tripping. Type A detection covers sinusoidal AC residual currents and pulsating DC residual currents. ## Mounting and installation Snaps onto DIN rail (REG). Mounting position any. Feed from top or bottom. Depth 70 mm, height 90 mm.","metaTitle":"Siemens 5SV3614-6KL SENTRON RCCB, 40 A, 300 mA, 2-Pole","metaDescription":"Siemens 5SV3614-6KL SENTRON RCCB, 40 A rated, 300 mA trip, Type A, instantaneous, 2-pole, 10 kA SCCR. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"N left","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Operating Frequency":"50 Hz","Product Designation":"RCCB","at AC / rated value":"40 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","I2t value / permissible":"58 000 A²·s","at 40 °C / rated value":"40 A","at 45 °C / rated value":"38.1 A","at 50 °C / rated value":"35.59 A","at 55 °C / rated value":"32.29 A","at 60 °C / rated value":"28.19 A","at 65 °C / rated value":"23.3 A","at 70 °C / rated value":"17.6 A","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Product Feature / Silicon-Free":"Yes","acc. to EN 60898 / rated value":"0.5 kA","For Testing Equipment / Minimum":"100 V","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"5 200 kA","Tripping Fault Current / Rated Value":"300 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Current Resistance / Rated Value":"1 kA","according to IEC 61008-1 / rated value":"0.5 kA","Switching Function / Short-Term Delayed":"No","size of installation devices / acc. to DIN 43880":"1","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$89.35","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=110960&mlfb=5SV3614-6KL","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV3614-6KL/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3614-6KL","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3614-6KL when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}