{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3614-8KL","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3614-8KL","canonicalUrl":"https://aoctrl.com/siemens/5SV3614-8KL","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3614-8KL","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3614-8KL, selective RCCB, 2-pole, 40 A, Type A, 300 mA residual, 10 kA SCCR, DIN rail mount, IP20.","salesMarkdown":"This is the part you spec when you need time-delayed tripping for selectivity downstream of a main RCD — it lets a fault clear on the branch without dropping the whole distribution board. ## Selectivity and trip coordination The selective design (S-type) means this RCCB withstands transient earth faults and inrush without tripping, so a downstream RCCB clears the fault first. Rated residual current is 300 mA — not the 30 mA you'd use for personal protection. That 300 mA threshold plus the intentional delay is what buys you coordination in a multi-level distribution panel. ## Temperature derating and installation That's unusual for a 40 A device and simplifies BOM validation. IP20 applies once the distribution board is installed and conductors are connected; treat it as a panel-internal device, not a field-mounted enclosure. Silicon-free construction is noted for environments where outgassing contaminates sensitive contacts or optics.","metaTitle":"Siemens 5SV3614-8KL SENTRON RCCB, 2-pole 40 A Type A 300 mA,","metaDescription":"Siemens 5SV3614-8KL SENTRON selective RCCB, 2-pole, 40 A, Type A, 300 mA residual, 10 kA SCCR. DIN rail mount. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"70 mm","Poles":"2","Width":"36 mm","Height":"90 mm","Mounting":"DIN rail (REG)","Product Status":"Active","Short Circuit Rating":"10 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bff9f13bdf38a668082284c2b9aafacc.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=627707&mlfb=5SV3614-8KL","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV3614-8KL/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3614-8KL","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3614-8KL when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}