{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3617-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3617-6","canonicalUrl":"https://aoctrl.com/siemens/5SV3617-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3617-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3617-6, 2-pole instantaneous RCCB, 80 A, 300 mA, type A, 230/400 V AC, 10 kA SCCR, DIN rail.","salesMarkdown":"The Siemens 5SV3617-6 is a 2-pole instantaneous RCCB from the SENTRON family, rated 80 A with a 300 mA type A residual operating current for 230/400 V AC 50 Hz systems. The 70 mm depth matches standard distribution board clearances, and the 60 mm grid spacing aligns with typical modular panel layouts. Top or bottom supply feed is allowed, and supplementary devices can be installed on the product extension. The 80 A rating governs continuous load capacity — sized for main incomer or heavy sub-feed duty on a 230/400 V three-phase system. The 300 mA type A residual detects pulsating DC fault currents (common from rectifiers, VFDs, and electronic loads) as well as sinusoidal AC, so it fits mixed-load panels where standard AC-type RCCBs might not trip. Being instantaneous (no short-time delay), it provides fast disconnection for personnel protection but must be coordinated with downstream selectivity if used as a main switch.","metaTitle":"Siemens 5SV3617-6 SENTRON RCCB, 80 A, 300 mA, Type A, 2-Pole","metaDescription":"Siemens 5SV3617-6 SENTRON 2-pole RCCB, 80 A rated, 300 mA residual, type A, instantaneous. 10 kA SCCR, 230/400 V AC, DIN rail. Active, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Grid Spacing":"60 mm","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"top or bottom","according to IEC 61008-1 rated value":"0.8 kA","Switching Function Short-Term Delayed":"No","Value Range Of The Operating Frequency":"50 Hz","value range of the supply voltage at AC":"230/400 V","Ambient Temperature During Storage Minimum":"-40 °C","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"100 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","Short-Circuit Current Of Series Fuse Maximum Permissible":"80 A","for rated value of the current at AC in hot operating state per pole":"3.9 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b9688dff694b38f9c4674cbd4c96fe97.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=463646&mlfb=5SV3617-6","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV3617-6/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SV3617-6?","answer":"The 5SV3617-6 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the difference between 5SV3617-6 and the 5SL4363-7 MCB?","answer":"The 5SV3617-6 is a 2-pole 80 A type A RCCB for residual protection, while the 5SL4363-7 is a 3-pole 63 A C-curve miniature circuit breaker (MCB) for overcurrent protection. They serve different functions — the RCCB detects earth leakage; the MCB protects against overloads and short circuits. They are not drop-in substitutes, though both mount on DIN rail in the same panel."},{"question":"What compliance documentation does Siemens provide for 5SV3617-6?","answer":"The 5SV3617-6 is designed to IEC 61008-1 and carries a 0.8 kA rated conditional short-circuit current per that standard. It is silicon-free. Specific RoHS, REACH, and UL documentation should be requested at quote time to match your compliance requirements."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3617-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3617-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}