{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3617-6KL","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3617-6KL","canonicalUrl":"https://aoctrl.com/siemens/5SV3617-6KL","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3617-6KL","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, Type A, 80 A, 300 mA, 2-pole, DIN rail, IP20.","salesMarkdown":"The 300 mA trip makes it a common choice for general socket-outlet circuits where a higher leakage threshold is acceptable to avoid nuisance tripping on equipment with natural leakage. The 80 A rating holds up to 40 °C; above that it derates — 77.87 A at 45 °C, 74.77 A at 50 °C, all the way down to 48.2 A at 70 °C. If your panel runs warm, size the upstream breaker for the derated current, not the 80 A nameplate. The short-circuit current rating is 10 kA per the manufacturer, though the IEC 61008-1 and EN 60898 ratings both list 0.8 kA — the higher 10 kA figure is the conditional SCCR with an upstream backup fuse or MCB. The let-through energy (I²t) is 110 000 A²·s, and the surge-current withstand is 1 kA (8/20 µs waveform), so it handles typical lightning-induced surges on a TT or TN-S system. Supply feeds from top or bottom — no forced orientation. IP20 with conductors connected, so it lives inside an enclosed distribution board, not out in a wet panel. Silicon-free construction, which matters if the board is in a coating or potting environment where silicone outgassing can contaminate contacts.","metaTitle":"Siemens 5SV3617-6KL SENTRON RCCB, Type A, 80A, 300mA, 2-Pole","metaDescription":"Siemens 5SV3617-6KL SENTRON RCCB, Type A, 80 A rated, 300 mA residual, 2-pole, DIN rail. IP20, current lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"N left","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Operating Frequency":"50 Hz","Product Designation":"RCCB","at AC / rated value":"80 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","I2t value / permissible":"110 000 A²·s","at 40 °C / rated value":"80 A","at 45 °C / rated value":"77.87 A","at 50 °C / rated value":"74.77 A","at 55 °C / rated value":"70.26 A","at 60 °C / rated value":"64.32 A","at 65 °C / rated value":"56.96 A","at 70 °C / rated value":"48.2 A","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Product Feature / Silicon-Free":"Yes","acc. to EN 60898 / rated value":"0.8 kA","For Testing Equipment / Minimum":"100 V","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"7 100 kA","Tripping Fault Current / Rated Value":"300 mA","Supply Voltage Frequency / Rated Value":"50 Hz","Surge Current Resistance / Rated Value":"1 kA","according to IEC 61008-1 / rated value":"0.8 kA","Switching Function / Short-Term Delayed":"No","size of installation devices / acc. to DIN 43880":"1","Mechanical Service Life (Operating Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/dfb23f5433b3daeb5b6859a08214862f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=414268&mlfb=5SV3617-6KL","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV3617-6KL/alternatives.json"},"ai":{"faq":[{"question":"Will 5SV3617-6KL drop into a panel specified around 5SY5250-7 without rewiring?","answer":"Both are DIN-rail (REG) mount, 2-module-width units, so the physical footprint and rail clip are identical. The terminal positions and supply orientation are the same (top or bottom feed). No rewiring needed for fit, but check the electrical ratings match your circuit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3617-6KL","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3617-6KL when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}