{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV3642-6","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV3642-6","canonicalUrl":"https://aoctrl.com/siemens/5SV3642-6","factsUrl":"https://aoctrl.com/api/mcp/products/5SV3642-6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV3642-6 RCCB, 4-pole Type A instantaneous, In 25 A, 300 mA, Un AC 400 V, 4 MW, 70 mm deep, DIN rail mount.","salesMarkdown":"The Siemens SENTRON 5SV3642-6 is a 4-pole residual current circuit breaker (RCCB), Type A instantaneous, rated 25 A with a 300 mA trip threshold for 400 V AC networks at 50 Hz. Rated for a short-circuit current of 10 kA per IEC 61008-1, with an additional 0.8 kA conditional rating. The supply can enter from the top or bottom. IP20 with the distribution board installed and conductors connected. Overvoltage category III. Silicon-free construction. Mechanical life is 10 000 cycles typical. Supplementary devices can be installed on the unit.","metaTitle":"Siemens 5SV3642-6 SENTRON RCCB, 4P, 25 A, 300 mA, 400 V AC","metaDescription":"Siemens SENTRON 5SV3642-6 RCCB, 4-pole, Type A, 25 A rated, 300 mA residual, 400 V AC. Active production. 4 MW units, 70 mm deep. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"72 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Grid Spacing":"60 mm","Number Of Poles":"4","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"4","Position Of Power Supply Cord":"top or bottom","according to IEC 61008-1 rated value":"0.8 kA","Switching Function Short-Term Delayed":"No","Value Range Of The Operating Frequency":"50 Hz","value range of the supply voltage at AC":"230/400 V","Ambient Temperature During Storage Minimum":"-40 °C","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"100 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","Short-Circuit Current Of Series Fuse Maximum Permissible":"80 A","for rated value of the current at AC in hot operating state per pole":"0.7 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$124.08","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ed280646498d532ac59ddeccc41d4200.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=160384&mlfb=5SV3642-6","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV3642-6/alternatives.json"},"ai":{"faq":[{"question":"What is 5SV3642-6's listed depth on this component line?","answer":"The installation depth is 70 mm, matching the overall depth dimension."},{"question":"What is 5SV3642-6's listed width on this component line?","answer":"Width is 72 mm, which corresponds to 4 modular width units at 18 mm each."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV3642-6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV3642-6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}