{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV4311-0","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV4311-0","canonicalUrl":"https://aoctrl.com/siemens/5SV4311-0","factsUrl":"https://aoctrl.com/api/mcp/products/5SV4311-0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, 2-pole, Type AC, In: 16 A, 30 mA, Un AC: 230 V, 10 kA SCCR, DIN rail mount, 70 mm depth.","salesMarkdown":"## RCCB for panel builders and MRO The Siemens 5SV4311-0 is a 2-pole residual current operated circuit breaker (RCCB) from the SENTRON family, rated 16 A with 30 mA trip sensitivity on a 230 V AC supply. The 30 mA threshold is the common personal-protection level per IEC 61008-1, sized to clear a ground fault before it becomes a shock hazard. Depth is 70 mm, which matches the standard SENTRON MCB/RCCB depth — it'll sit flush in a panel alongside 5SL or 5SY series breakers without protruding past the busbar cover. Mounting position is unrestricted, and supply can land top or bottom, which saves a few minutes when you're retrofitting into a crowded enclosure. In a 230 V residential or light commercial panel fed by a transformer of typical impedance, 10 kA covers most installations; if your available fault current exceeds that, you'll need an upstream current-limiting fuse or MCB rated higher. The permissible series fuse is capped at 63 A, so don't oversize the backup protection. IP20 with connected conductors — fine inside a distribution board where the enclosure provides the outer IP rating. Not for wet or washdown locations without a separate cabinet.","metaTitle":"Siemens 5SV4311-0 SENTRON RCCB, 2-pole, 16 A, 30 mA, 230 V A","metaDescription":"Siemens 5SV4311-0 SENTRON RCCB, 2-pole Type AC, 16 A, 30 mA, 230 V AC. Active production. DIN rail mount, 10 kA SCCR. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Grid Spacing":"60 mm","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"top or bottom","according to IEC 61008-1 rated value":"0.5 kA","Switching Function Short-Term Delayed":"No","Value Range Of The Operating Frequency":"50 Hz","value range of the supply voltage at AC":"230 V","Ambient Temperature During Storage Minimum":"-40 °C","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"195 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","Short-Circuit Current Of Series Fuse Maximum Permissible":"63 A","for rated value of the current at AC in hot operating state per pole":"0.4 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ffb01e353966b1eea2a85c88c47c2a58.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=158465&mlfb=5SV4311-0","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV4311-0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SV4311-0 and how do I get a price?","answer":"The 5SV4311-0 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"Will 5SV4311-0 drop into a panel that was specified around 5SL4363-7 without rewiring?","answer":"No — the 5SL4363-7 is a 3-pole miniature circuit breaker (MCB), not an RCCB. The 5SV4311-0 is a 2-pole RCCB with a different function (residual current protection vs overcurrent protection). They share the same 70 mm depth and DIN rail mounting, but the wiring and circuit protection scheme are different. You cannot simply swap one for the other without redesigning the circuit."},{"question":"What compliance documentation does Siemens provide for 5SV4311-0?","answer":"The 5SV4311-0 is designed to IEC 61008-1. Siemens typically provides a declaration of conformity (CE), and the product carries the SENTRON brand. For specific RoHS, REACH, or UL documentation, request the manufacturer's compliance declaration at quote time — the evidence does not list a UL mark or specific RoHS/REACH statement for this order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV4311-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV4311-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}