{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV4316-0KK13","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV4316-0KK13","canonicalUrl":"https://aoctrl.com/siemens/5SV4316-0KK13","factsUrl":"https://aoctrl.com/api/mcp/products/5SV4316-0KK13","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, 5SV4316-0KK13, 2-pole, 63 A rated, 30 mA residual current, Type AC, instantaneous, 10 kA SCCR, DIN rail mount.","salesMarkdown":"The Type AC designation means it responds only to sinusoidal alternating residual currents; it will not reliably detect pulsating DC or smooth DC faults, so this part stays in AC-only circuits like lighting, socket outlets, and general-purpose power distribution. The 63 A rating holds flat across ambient temperatures from 40 °C to 55 °C (–), then derates to 56.96 A at 65 °C and 48.2 A at 70 °C (–). That means in a warm panel (say 60 °C internal), you still get the full 63 A; at 70 °C you lose about 23 % of capacity. The breaking capacity per EN 60898 is 0.8 kA, which is the conditional short-circuit withstand when the RCCB is backed by an upstream MCB. For coordination, the 10 kA SCCR is the figure that governs the installation's fault-withstand rating. Mounting position is any; supply can enter from top or bottom. The IP20 rating applies only when installed in a distribution board with conductors connected — the RCCB itself is not sealed against dust or moisture. Silicon-free construction is noted for applications where outgassing would contaminate sensitive contacts or optics.","metaTitle":"Siemens 5SV4316-0KK13 SENTRON RCCB, 2P, 63 A, 30 mA, Type AC","metaDescription":"Siemens SENTRON 5SV4316-0KK13 RCCB, 2-pole, 63 A rated, 30 mA trip, Type AC, 10 kA SCCR. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV4316-0KK13","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, Type AC, In: 63 A, 30 mA, Un AC: 24-125 V","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"Un AC: 24-125 V","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Operating Frequency":"50 Hz","Product Designation":"RCCB","at AC / rated value":"63 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","I2t value / permissible":"110 000 A²·s","at 40 °C / rated value":"63 A","at 45 °C / rated value":"63 A","at 50 °C / rated value":"63 A","at 55 °C / rated value":"63 A","at 60 °C / rated value":"63 A","at 65 °C / rated value":"56.96 A","at 70 °C / rated value":"48.2 A","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Product Feature / Silicon-Free":"Yes","acc. to EN 60898 / rated value":"0.8 kA","For Testing Equipment / Minimum":"24 V","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"7 100 kA","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","according to IEC 61008-1 / rated value":"0.8 kA","Switching Function / Short-Term Delayed":"No","size of installation devices / acc. to DIN 43880":"1","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4654cae4faee74fef1b0f09339815534.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=627713&mlfb=5SV4316-0KK13"},"ai":{"faq":[{"question":"What is 5SV4316-0KK13's listed depth (70 mm) on this component line?","answer":"The installation depth is 70 mm, matching the overall depth of 70 mm. This is the dimension from the DIN rail mounting surface to the front of the device."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV4316-0KK13","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV4316-0KK13 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}