{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV4316-0KL","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV4316-0KL","canonicalUrl":"https://aoctrl.com/siemens/5SV4316-0KL","factsUrl":"https://aoctrl.com/api/mcp/products/5SV4316-0KL","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, 2-pole, 63 A, 30 mA, Type AC, instantaneous, 10 kA, 230 V AC, 50 Hz, DIN rail, 36 mm width.","salesMarkdown":"It's designed for instantaneous tripping — no intentional delay — so it clears a ground fault as fast as the waveform allows. Mounts on a DIN rail (REG) in any orientation. Installation depth is 70 mm, matching the overall depth. Rated current holds at 63 A from 40 °C through 55 °C ambient. At 60 °C it's still 63 A. Derating starts at 65 °C (56.96 A) and drops to 48.2 A at 70 °C. At 65 °C you lose about 10 % of the 63 A rating; at 70 °C it's down to 48.2 A — roughly 76 % of nominal. Panel builders should check the internal ambient before assuming full 63 A continuous duty. ## Integration notes DIN-rail snap-on, any mounting position. The N terminal is on the left (product variation 'N left'). Silicon-free construction is a plus for environments where silicone outgassing can contaminate contacts or optics — common in automotive paint shops or semiconductor fabs. The let-through current (I²t) is 110 000 A²·s; peak let-through is 7 100 A. These numbers help with selective coordination studies.","metaTitle":"Siemens 5SV4316-0KL SENTRON RCCB, 2-pole 63A 30mA Type AC, 1","metaDescription":"Siemens 5SV4316-0KL SENTRON 2-pole RCCB, 63 A rated, 30 mA trip, Type AC, 10 kA SCCR. Current lifecycle. Sourced to order against RFQ. DIN rail mount, 36 mm wide.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV4316-0KL","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, Type AC, In: 63 A, 30 mA, Un AC: 230 V, N left","Grid Spacing":"60 mm","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"63 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"N left","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","I2t value permissible":"110 000 A²·s","Residual Current Type":"AC","at 40 °C rated value":"63 A","at 45 °C rated value":"63 A","at 50 °C rated value":"63 A","at 55 °C rated value":"63 A","at 60 °C rated value":"63 A","at 65 °C rated value":"56.96 A","at 70 °C rated value":"48.2 A","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"top or bottom","Let-Through Current Permissible":"7 100 A","Tripping Fault Current Rated Value":"30 mA","according to IEC 61008-1 rated value":"0.8 kA","Switching Function Short-Term Delayed":"No","Value Range Of The Operating Frequency":"50 Hz","value range of the supply voltage at AC":"230 V","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"195 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","Short-Circuit Current Of Series Fuse Maximum Permissible":"80 A","for rated value of the current at AC in hot operating state per pole":"5.3 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a0b6d462448684fc340e055dfe2ce5ac.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=35959&mlfb=5SV4316-0KL"},"ai":{"faq":[{"question":"What is the 5SV4316-0KL's width and depth?","answer":"Width is 36 mm (2 modular units on 60 mm grid spacing). Depth is 70 mm, matching the installation depth."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV4316-0KL","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV4316-0KL when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}