{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV4342-0GV01","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV4342-0GV01","canonicalUrl":"https://aoctrl.com/siemens/5SV4342-0GV01","factsUrl":"https://aoctrl.com/api/mcp/products/5SV4342-0GV01","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, 4-pole, AC type, 25 A, 30 mA, instantaneous, 10 kA SCCR, 50 Hz, DIN rail mount, IP20, current lifecycle.","salesMarkdown":"It's an AC-type device — that means it detects sinusoidal AC residual currents only, not pulsating DC or smooth DC. The 25 A rating holds flat from 40 °C through 60 °C, only starting to derate at 65 °C (23.3 A) and 70 °C (17.6 A), so in a warm enclosure it keeps its full rating through most normal operating conditions. The 5SV4342-0GV01 carries a 10 kA short-circuit current rating (SCCR) per IEC 61008-1, and 0.8 kA conditional rating per EN 60898. The I²t let-through is 58,000 A²·s, and the permissible let-through current peak is 5,200 A — both numbers a coordination engineer would use when sizing upstream protection. ## Integration notes DIN rail mount, 4 MW wide, 70 mm deep — it fits any standard SENTRON distribution board or enclosure. The IP20 rating applies only when installed in a distribution board with conductors connected, so it's not a standalone outdoor device. Silicon-free construction is specified, which matters for potting or conformal coating processes in certain industrial panels. Overvoltage category III means it's rated for fixed-installation distribution level, not for downstream socket outlets. The switching function is instantaneous — no short-time delay — so it trips immediately on a 30 mA fault. That's fine for personal protection, but if you have equipment with natural leakage (VFDs, UPS, switching supplies) that could cause nuisance tripping, you'd want a time-delayed or selective type (S-type) RCCB instead.","metaTitle":"Siemens 5SV4342-0GV01 SENTRON RCCB, 4-pole, 25 A, 30 mA, AC","metaDescription":"Siemens SENTRON 5SV4342-0GV01 RCCB, 4-pole, 25 A rated, 30 mA trip, AC residual current type, 10 kA SCCR, 50 Hz, DIN rail mount, current lifecycle. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"72 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Number Of Poles":"4","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"Bulk packaging 18 units","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Operating Frequency":"50 Hz","Product Designation":"RCCB","at AC / rated value":"25 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","I2t value / permissible":"58 000 A²·s","at 40 °C / rated value":"25 A","at 45 °C / rated value":"25 A","at 50 °C / rated value":"25 A","at 55 °C / rated value":"25 A","at 60 °C / rated value":"25 A","at 65 °C / rated value":"23.3 A","at 70 °C / rated value":"17.6 A","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"4","Product Feature / Silicon-Free":"Yes","acc. to EN 60898 / rated value":"0.8 kA","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"5 200 kA","Tripping Fault Current / Rated Value":"30 mA","Supply Voltage Frequency / Rated Value":"50 Hz","according to IEC 61008-1 / rated value":"0.8 kA","Switching Function / Short-Term Delayed":"No","size of installation devices / acc. to DIN 43880":"1","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/123f84553a8a3025eba30e82a74cf0e1.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=572877&mlfb=5SV4342-0GV01","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV4342-0GV01/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for 5SV4342-0GV01?","answer":"4-pole, 25 A rated, 30 mA trip sensitivity, AC residual current type, 10 kA SCCR, 50 Hz only, DIN rail mount, 4 MW wide, IP20 when installed in a distribution board."},{"question":"Where can I buy 5SV4342-0GV01?","answer":"We source and quote this part to order against an RFQ through independent industrial distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"Will 5SV4342-0GV01 drop into a panel specified around 5SL4363-7 without rewiring?","answer":"Not without checking. Both are SENTRON DIN-rail devices with the same 70 mm depth and 4 MW width, so the mechanical fit is the same. But the electrical ratings differ — verify the pole count, current rating, and trip characteristic of the original 5SL4363-7 specification before swapping. The 5SV4342-0GV01 is a 4-pole 25 A 30 mA AC-type; if the original called for a different pole count, current, or type (A, F, or B), this won't be a direct replacement."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV4342-0GV01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV4342-0GV01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}