{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV4412-0","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV4412-0","canonicalUrl":"https://aoctrl.com/siemens/5SV4412-0","factsUrl":"https://aoctrl.com/api/mcp/products/5SV4412-0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV4412-0, 2-pole RCCB, Type AC, In 25 A, 100 mA, Un AC 230 V, DIN rail mount, active production.","salesMarkdown":"The Siemens 5SV4412-0 is a 2-pole residual current circuit breaker (RCCB) from the SENTRON family, Type AC, rated 25 A with a 100 mA trip threshold at 230 V AC. That 100 mA sensitivity is sized for equipment protection rather than personnel shock — it catches insulation degradation on fixed wiring or motor windings before leakage climbs high enough to trip a 30 mA device, provided the downstream circuit is coordinated for it. The 100 mA residual sensitivity is instantaneous (no intentional delay), so it clears earth faults within the standard trip curve for Type AC devices, which detect sinusoidal AC leakage only. Supply voltage is 230/400 V AC, 50 Hz only — this unit is not rated for 60 Hz operation. The 2-pole construction switches both phase and neutral on a single-phase supply or one phase plus neutral on a three-phase system. IP20 rating applies only when the distribution board cover is installed and conductors are connected — bare terminals are not finger-safe. The grid spacing of 60 mm matches standard European distribution board cutouts.","metaTitle":"Siemens 5SV4412-0 SENTRON RCCB, 2-pole, 25 A, 100 mA, Type A","metaDescription":"Siemens 5SV4412-0 SENTRON RCCB, 2-pole, Type AC, rated 25 A / 100 mA at 230 V AC. Active production. DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Grid Spacing":"60 mm","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"top or bottom","according to IEC 61008-1 rated value":"0.5 kA","Switching Function Short-Term Delayed":"No","Value Range Of The Operating Frequency":"50 Hz","value range of the supply voltage at AC":"230/400 V","Ambient Temperature During Storage Minimum":"-40 °C","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"100 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","Short-Circuit Current Of Series Fuse Maximum Permissible":"63 A","for rated value of the current at AC in hot operating state per pole":"0.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=503312&mlfb=5SV4412-0","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV4412-0/alternatives.json"},"ai":{"faq":[{"question":"What is 5SV4412-0 used for?","answer":"The 5SV4412-0 is a 2-pole residual current circuit breaker (RCCB) rated 25 A with 100 mA sensitivity, Type AC. It protects circuits against earth faults by disconnecting when sinusoidal AC leakage exceeds 100 mA, typically used for equipment protection on fixed wiring, motor feeders, or sub-distribution boards in commercial and industrial installations."},{"question":"Where can I buy 5SV4412-0?","answer":"The 5SV4412-0 is available to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not on this listing. Volume and blanket orders are quoted on request."},{"question":"What are the key specifications of 5SV4412-0?","answer":"2-pole RCCB, Type AC, rated 25 A, 100 mA residual current, 230 V AC supply voltage, 10 kA SCCR per IEC 61008-1, 50 Hz only, DIN rail mount, 2 modular width units (36 mm), IP20 with distribution board cover installed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV4412-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV4412-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}