{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV4414-0","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV4414-0","canonicalUrl":"https://aoctrl.com/siemens/5SV4414-0","factsUrl":"https://aoctrl.com/api/mcp/products/5SV4414-0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, instantaneous, Type AC, 2-pole, 40 A rated, 100 mA trip, 10 kA SCCR, 230/400 V AC, 50 Hz, DIN-rail mount, IP20.","salesMarkdown":"The Siemens SENTRON 5SV4414-0 is a 2-pole residual current circuit breaker (RCCB) rated at 40 A with a 100 mA trip threshold, Type AC, for 230/400 V AC 50 Hz systems. It carries a 10 kA short-circuit current rating (SCCR) per IEC 61008-1 and mounts on a DIN rail (REG) — two modular width units wide, so it occupies 36 mm on the rail. The 100 mA trip suits circuits where a higher threshold is needed to avoid nuisance tripping from leakage in equipment with filters or long cable runs, while still providing earth-fault protection. The 40 A rating holds at 40 °C ambient; at 45 °C it derates to 38.1 A, and at 55 °C to 32.29 A. At 70 °C the continuous current drops to 17.6 A. The RCCB is rated for any mounting position and accepts top or bottom supply feed. Depth is 70 mm — standard for a 2-MW SENTRON RCCB — so it clears a 100 mm deep enclosure without issue. IP20 protection applies once the distribution board is installed with conductors connected; the housing is silicone-free.","metaTitle":"Siemens SENTRON 5SV4414-0 RCCB, 40 A, 100 mA, 2-pole","metaDescription":"Siemens SENTRON 5SV4414-0 RCCB, 40 A rated, 100 mA trip, 2-pole, Type AC, 10 kA SCCR, 230/400 V. DIN-rail mount. Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"40 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","I2t value permissible":"58 000 A²·s","Residual Current Type":"AC","at 40 °C rated value":"40 A","at 45 °C rated value":"38.1 A","at 50 °C rated value":"35.59 A","at 55 °C rated value":"32.29 A","at 60 °C rated value":"28.19 A","at 65 °C rated value":"23.3 A","at 70 °C rated value":"17.6 A","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"top or bottom","Let-Through Current Permissible":"5 200 A","Tripping Fault Current Rated Value":"100 mA","according to IEC 61008-1 rated value":"0.5 kA","Switching Function Short-Term Delayed":"No","Value Range Of The Operating Frequency":"50 Hz","value range of the supply voltage at AC":"230/400 V","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"100 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","Short-Circuit Current Of Series Fuse Maximum Permissible":"63 A","for rated value of the current at AC in hot operating state per pole":"1.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/df2008bb898b09d4b01fbe66abf5263d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=104129&mlfb=5SV4414-0","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV4414-0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 5SV4414-0 and how do I get a price?","answer":"The 5SV4414-0 is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to receive current pricing and availability."},{"question":"What is 5SV4414-0's listed depth (70 mm) on this component line?","answer":"The depth is 70 mm, which is the standard depth for a 2-module-width SENTRON RCCB and fits typical 100 mm deep enclosures."},{"question":"What is 5SV4414-0's listed width (36 mm) on this component line?","answer":"The width is 36 mm, corresponding to 2 modular width units (MW) on a DIN rail."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV4414-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV4414-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}