{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV4416-0","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV4416-0","canonicalUrl":"https://aoctrl.com/siemens/5SV4416-0","factsUrl":"https://aoctrl.com/api/mcp/products/5SV4416-0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV4416-0, 2-pole RCCB, 63 A rated, 100 mA AC type, 10 kA SCCR, IP20, DIN-rail mount.","salesMarkdown":"The Siemens SENTRON 5SV4416-0 is a 2-pole residual-current circuit breaker (RCCB) rated for 63 A continuous at 40 °C, with a 100 mA AC-type tripping threshold. That 100 mA sensitivity is the go-to for general socket-outlet circuits and feeder protection where a lower 30 mA threshold would cause nuisance trips on longer cable runs. Snaps onto DIN rail (REG) and takes up 2 modular-width units (36 mm wide). Depth is 70 mm, so it sits flush with most 12-module enclosures — no surprise when you're packing a sub-distribution board. The IP20 rating is standard for a distribution board interior; only the front face is touch-safe once wired. ## Thermal derating and real-world loading Full 63 A holds from 40 °C up to 60 °C — no derating in that band. At 65 °C it drops to 56.96 A, and at 70 °C to 48.2 A. The 50 Hz operating frequency is fixed; this is not a 60 Hz variant.","metaTitle":"Siemens 5SV4416-0 SENTRON RCCB, 2-pole 63A 100mA AC type, 10","metaDescription":"Siemens 5SV4416-0 SENTRON RCCB, 2-pole, 63 A rated, 100 mA AC type, 10 kA SCCR, IP20. Current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"63 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","I2t value permissible":"110 000 A²·s","Residual Current Type":"AC","at 40 °C rated value":"63 A","at 45 °C rated value":"63 A","at 50 °C rated value":"63 A","at 55 °C rated value":"63 A","at 60 °C rated value":"63 A","at 65 °C rated value":"56.96 A","at 70 °C rated value":"48.2 A","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"top or bottom","Let-Through Current Permissible":"7 100 A","Tripping Fault Current Rated Value":"100 mA","according to IEC 61008-1 rated value":"0.8 kA","Switching Function Short-Term Delayed":"No","Value Range Of The Operating Frequency":"50 Hz","value range of the supply voltage at AC":"230/400 V","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"100 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","Short-Circuit Current Of Series Fuse Maximum Permissible":"80 A","for rated value of the current at AC in hot operating state per pole":"2.7 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8073a4ebc41a4582915d28e9208b0408.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=59223&mlfb=5SV4416-0","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV4416-0/alternatives.json"},"ai":{"faq":[{"question":"Who supplies 5SV4416-0 and how is it quoted for volume purchases?","answer":"We source and quote this part to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is 5SV4416-0's listed depth?","answer":"70 mm, which is standard for this class of SENTRON RCCB and fits typical distribution board depths."},{"question":"What compliance documentation does this brand provide for 5SV4416-0?","answer":"The part is designed to IEC 61008-1 and carries a silicon-free designation. Standard Siemens declarations for RoHS and REACH are available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV4416-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV4416-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}