{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV4614-0","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV4614-0","canonicalUrl":"https://aoctrl.com/siemens/5SV4614-0","factsUrl":"https://aoctrl.com/api/mcp/products/5SV4614-0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, 5SV4614-0, AC type, instantaneous, 2-pole, 40 A rated, 300 mA trip, 10 kA SCCR, 230/400 V AC, 50 Hz, DIN rail mount, 2 MW, IP20.","salesMarkdown":"Mounting position any; supply can come from top or bottom. Grid spacing 60 mm matches standard distribution board pitch. Silicon-free construction suits applications where outgassing must be avoided, like clean rooms or sealed enclosures. At 45 °C it derates to 38.1 A, at 50 °C to 35.59 A, at 55 °C to 32.29 A, at 60 °C to 28.19 A, at 65 °C to 23.3 A, and at 70 °C to 17.6 A. ## Fault energy and coordination Let-through current permissible 5 200 A; I²t value 58 000 A²s. These numbers drive selectivity with upstream protective devices — the 5SV4614-0 lets through less energy than a typical 63 A MCB, so you can coordinate downstream without nuisance trips. Rated conditional short-circuit current per IEC 61008-1 is 0.5 kA — that's the withstand under the standard; the 10 kA SCCR is the practical interrupting rating for the installation.","metaTitle":"Siemens SENTRON 5SV4614-0 RCCB, 40A 300mA AC Type, 2-Pole","metaDescription":"Siemens SENTRON 5SV4614-0 RCCB, 40 A rated, 300 mA trip, AC type, 2-pole, 10 kA SCCR, 230/400 V, 50 Hz. DIN rail mount. Current lifecycle. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV4614-0","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, Type AC, In: 40 A, 300 mA, Un AC: 230 V","Grid Spacing":"60 mm","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"40 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","I2t value permissible":"58 000 A²·s","Residual Current Type":"AC","at 40 °C rated value":"40 A","at 45 °C rated value":"38.1 A","at 50 °C rated value":"35.59 A","at 55 °C rated value":"32.29 A","at 60 °C rated value":"28.19 A","at 65 °C rated value":"23.3 A","at 70 °C rated value":"17.6 A","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"top or bottom","Let-Through Current Permissible":"5 200 A","Tripping Fault Current Rated Value":"300 mA","according to IEC 61008-1 rated value":"0.5 kA","Switching Function Short-Term Delayed":"No","Value Range Of The Operating Frequency":"50 Hz","value range of the supply voltage at AC":"230/400 V","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"100 V","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","Short-Circuit Current Of Series Fuse Maximum Permissible":"63 A","for rated value of the current at AC in hot operating state per pole":"1.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$26.67","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a907e617a926348f297b82315380e96d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=468234&mlfb=5SV4614-0"},"ai":{"faq":[{"question":"What is 5SV4614-0's depth?","answer":"70 mm. That's the installed depth from the DIN rail face to the back of the device."},{"question":"What is 5SV4614-0's width?","answer":"36 mm, which corresponds to 2 modular width units on a standard DIN-rail grid."},{"question":"Will 5SV4614-0 drop into a panel specified around 5SL4363-7 without rewiring?","answer":"No — 5SL4363-7 is a miniature circuit breaker (MCB), not an RCCB. The 5SV4614-0 is a residual current device and requires different wiring (line + neutral through the RCCB). They are not drop-in interchangeable."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV4614-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV4614-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}