{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV4614-0KL","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV4614-0KL","canonicalUrl":"https://aoctrl.com/siemens/5SV4614-0KL","factsUrl":"https://aoctrl.com/api/mcp/products/5SV4614-0KL","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV4 series RCCB, 2-pole, 40 A rated current at 40 °C, 300 mA residual, AC-type fault current, instantaneous, 10 kA SCCR, IP20, 2 width units (36 mm), DIN-rail mount.","salesMarkdown":"Rated 40 A at 40 °C ambient, with a derating curve that drops to 17.62 A at 70 °C. ## Wire range and termination That's a wide enough clamp to handle a 40 A feed with a 10 mm² conductor and still fit a 35 mm² incoming if the panel design calls for it. Supply can land top or bottom — no polarity worry on an RCCB, but keep the neutral on the N-left side (product variation N left). Rated IP20 with connected conductors in an installed distribution board.","metaTitle":"Siemens 5SV4614-0KL SENTRON RCCB, 2-pole, 40 A, 300 mA, AC t","metaDescription":"Siemens SENTRON 5SV4614-0KL 2-pole RCCB, 40 A rated at 40 °C, 300 mA residual, AC type, 10 kA SCCR, IP20, current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Solid":"0.75 ... 35 mm²","Width":"36 mm","title":"5SV4614-0KL","Height":"90 mm","Stranded":"0.75 ... 35 mm²","at 40 Cel":"40 A","at 45 Cel":"38.1 A","at 50 Cel":"35.59 A","at 55 Cel":"32.29 A","at 60 Cel":"28.19 A","at 65 Cel":"23.3 A","at 70 Cel":"17.62 A","Rated Value":"50 Hz","description":"Residual current operated circuit breaker, 2-pole, Type AC, In: 40 A, 300 mA, Un AC: 230 V, N left","Mounting type":"DIN rail (REG)","During Storage":"-40 ... +75 °C","Number of poles":"2","lifecycle_stage":"current","Mounting position":"any","Installation depth":"70 mm","Product brand name":"SENTRON","Product variations":"N left","Ambient temperature":"-25 ... +45 °C","Product designation":"RCCB","Protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage category":"III","Design of the product":"Instantaneous","Number of width units":"2","Type of fault current":"AC","acc. to DIN EN 61346-2":"F","acc. to DIN EN 81346-2":"F","I2t-value / permissible":"58 000 A²·s","circuit-breaker / Design":"5SV4","Short-circuit current rating":"10 kA","Current / at AC / rated value":"40 A","Product feature / silicon-free":"Yes","Position / of power supply cord":"top or bottom","Protection against electrical shock":"Finger and back-of-hand safe","Supply voltage / at AC / rated value":"230/400 V","Switching function / short-term delayed":"No","Tripping residual current / rated value":"300 mA","Tightening torque / with screw-type terminals":"2.5 ... 3 N·m","Size of installation devices / acc. to DIN 43880":"1","Supply voltage / for testing equipment / minimum":"100 V","Mechanical service life (switching cycles) / typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/afbcae837515a6d695caaf2c21cf8e34.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=112214&mlfb=5SV4614-0KL"},"ai":{"faq":[{"question":"What is the depth of the 5SV4614-0KL?","answer":"70 mm — that's the installed depth including the DIN-rail clip. The panel depth needs at least 70 mm clearance from the rail face to the cover."},{"question":"Will the 5SV4614-0KL replace a 5SU9354-7KK16 without rewiring?","answer":"Both are 2-pole 40 A 300 mA AC-type RCCBs with similar DIN-rail footprint, but the 5SV4 is instantaneous (no short-time delay) and uses a different housing. The terminal layout and neutral position (N left) are the same, so it should drop in mechanically. Verify the DIN clip alignment — the 5SU9 series has a slightly different latch profile. No rewiring needed if the terminals match."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV4614-0KL","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV4614-0KL when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}