{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV4617-0","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV4617-0","canonicalUrl":"https://aoctrl.com/siemens/5SV4617-0","factsUrl":"https://aoctrl.com/api/mcp/products/5SV4617-0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, 2-pole, Type AC, In 80 A, IΔn 300 mA, Un AC 230 V, 10 kA SCCR, DIN rail mount, IP20.","salesMarkdown":"The Siemens SENTRON 5SV4617-0 is a 2-pole residual current operated circuit breaker (RCCB), Type AC, rated 80 A with a 300 mA trip threshold, for 230 V AC 50 Hz systems. The IP20 rating applies once the board is installed with conductors connected, so keep it inside an enclosure. The 80 A rating holds at 40 °C ambient; at 45 °C it derates to 77.87 A, and at 55 °C to 70.26 A — so if your distribution board runs hot, factor the derating curve into the load. The 300 mA residual-current trip is an instantaneous Type AC design (sine-wave AC faults only), not short-time delayed, so it's suited for general shock and fire protection on circuits without electronics generating pulsed DC faults. The test circuit requires a minimum 100 V to operate the test button.","metaTitle":"Siemens SENTRON 5SV4617-0 RCCB, 2-pole, 80 A, 300 mA, Type A","metaDescription":"Siemens SENTRON 5SV4617-0 RCCB, 2-pole, 80 A, 300 mA trip, Type AC, 10 kA SCCR, DIN rail mount, IP20. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV4617-0","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, Type AC, In: 80 A, 300 mA, Un AC: 230 V","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Operating Frequency":"50 Hz","Product Designation":"RCCB","at AC / rated value":"80 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","I2t value / permissible":"110 000 A²·s","at 40 °C / rated value":"80 A","at 45 °C / rated value":"77.87 A","at 50 °C / rated value":"74.77 A","at 55 °C / rated value":"70.26 A","at 60 °C / rated value":"64.32 A","at 65 °C / rated value":"56.96 A","at 70 °C / rated value":"48.2 A","Short-Circuit Current Rating":"10 kA","Number Of Modular Width Units":"2","Product Feature / Silicon-Free":"Yes","For Testing Equipment / Minimum":"100 V","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"7 100 A","Tripping Fault Current / Rated Value":"300 mA","Supply Voltage Frequency / Rated Value":"50 Hz","according to IEC 61008-1 / rated value":"0.8 kA","Switching Function / Short-Term Delayed":"No","Mechanical Service Life (Switching Cycles) / Typical":"10 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0e4aebb0e77a7a63decb61e1b9444c26.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=380429&mlfb=5SV4617-0"},"ai":{"faq":[{"question":"What is the closest functional alternative to 5SV4617-0?","answer":"The 5SU9354-7KK20 is a peer in the same SENTRON family — also a 2-pole RCCB, Type AC, 80 A, 300 mA, DIN rail mount — but check the exact width and depth dimensions against your panel layout; the 5SV4617-0 is 36 mm wide and 70 mm deep."},{"question":"Where can I buy 5SV4617-0?","answer":"Sourced and quoted to order against an RFQ through independent distribution — availability and current pricing confirmed at quote time."},{"question":"What compliance documentation does Siemens provide for 5SV4617-0?","answer":"The part is designed to IEC 61008-1, carries a 0.8 kA rated short-circuit capacity per that standard, and is marked as silicon-free. RoHS, REACH, and UL documentation should be available from Siemens upon request; the evidence does not list specific certificates."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV4617-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV4617-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}