{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV5111-0","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV5111-0","canonicalUrl":"https://aoctrl.com/siemens/5SV5111-0","factsUrl":"https://aoctrl.com/api/mcp/products/5SV5111-0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV5111-0 RCCB, 2-pole, Type AC, In 16 A, 10 mA trip, Un AC 230 V, 6 kA SCCR, DIN rail mount, 2 MW width.","salesMarkdown":"The Siemens SENTRON 5SV5111-0 is a 2-pole residual current operated circuit breaker (RCCB) rated 16 A at 230/400 VAC, 50 Hz, with a 10 mA trip threshold and Type AC waveform detection. It protects against earth faults by disconnecting both poles when leakage exceeds 10 mA — sized for circuits where very low leakage is the safety threshold, like wet locations or equipment with sensitive ground-fault requirements. The 10 mA trip is unusually sensitive; standard RCCBs are 30 mA. That means it catches leakage currents a 30 mA device would miss, but it also risks nuisance tripping on circuits with normal capacitive leakage (long cable runs, surge suppressors). Use it where 10 mA is code-mandated or the equipment requires it — not as a general-purpose replacement for a 30 mA RCCB. Short-circuit withstand is 6 kA per IEC 61008-1. The let-through energy is capped at 58 000 A²·s and peak let-through current at 5 200 A — numbers a panel designer uses to coordinate with the upstream MCB or fuse so the RCCB isn't asked to clear a fault beyond its rating. The maximum permissible series fuse is 63 A. Type AC detection means it trips on sinusoidal residual AC current only. It will not detect pulsating DC or smooth DC faults — if the load includes rectifiers, VFDs, or switching power supplies, a Type A or Type B RCCB is the correct choice. This part is for plain AC circuits with no electronic load generating DC fault content. Snaps onto DIN rail (REG) — 36 mm wide, 2 modular-width units. Depth is 70 mm, installation depth the same. Grid spacing is 60 mm, the standard DIN pitch for enclosure cutouts. Mounting position is any orientation; supply can enter top or bottom.","metaTitle":"Siemens 5SV5111-0 SENTRON RCCB, 2-pole, 16 A, 10 mA, Type AC","metaDescription":"Siemens SENTRON 5SV5111-0 RCCB, 2-pole, 16 A rated, 10 mA trip, Type AC, 6 kA SCCR, 230/400 VAC, 50 Hz. DIN rail mount. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV5111-0","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, Type AC, In: 16 A, 10 mA, Un AC: 230 V","Grid Spacing":"60 mm","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"16 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","I2t value permissible":"58 000 A²·s","Residual Current Type":"AC","at 40 °C rated value":"16 A","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"6 kA","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"top or bottom","Let-Through Current Permissible":"5 200 A","Tripping Fault Current Rated Value":"10 mA","according to IEC 61008-1 rated value":"0.5 kA","Switching Function Short-Term Delayed":"No","Value Range Of The Operating Frequency":"50 Hz","value range of the supply voltage at AC":"230/400 V","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"100 V","Mechanical Service Life (Operating Cycles) Typical":"2 000","Product Extension Installable Supplementary Devices":"No","Short-Circuit Current Of Series Fuse Maximum Permissible":"63 A","for rated value of the current at AC in hot operating state per pole":"0.7 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b06fcab8fd31e0cc802a854f6addb38a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=224140&mlfb=5SV5111-0"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SV5111-0?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"Will 5SV5111-0 drop into a panel specified around 5SL6550-7BB without rewiring?","answer":"Both are 2-pole RCCBs on DIN rail, but verify the trip rating and type — the 5SV5111-0 is 10 mA Type AC; the 5SL6550-7BB carries different ratings. The physical footprint (2 MW, 36 mm wide) is the same, so it fits the rail and busbar position, but the electrical function may not be a direct swap without checking the circuit's leakage requirements."},{"question":"What compliance documentation does this brand provide for 5SV5111-0?","answer":"The part carries IEC 61008-1 certification for RCCB performance. As a Siemens SENTRON product, it typically ships with CE marking and manufacturer declarations of conformity; specific RoHS/REACH declarations are available from Siemens documentation portals or on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV5111-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV5111-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}