{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV5311-6KL","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV5311-6KL","canonicalUrl":"https://aoctrl.com/siemens/5SV5311-6KL","factsUrl":"https://aoctrl.com/api/mcp/products/5SV5311-6KL","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV5311-6KL, residual current operated circuit breaker (RCCB), 2-pole, Type A, In: 16 A, 30 mA, Un AC: 230 V, N left, DIN rail mount.","salesMarkdown":"The Siemens 5SV5311-6KL is a 2-pole residual current operated circuit breaker (RCCB) from the SENTRON family, rated 16 A at 230 V AC, 50 Hz, with a 30 mA trip threshold and Type A residual current sensitivity. The 30 mA trip current (Type A) catches pulsating DC fault currents as well as sinusoidal AC — common in circuits with rectifiers, variable-speed drives, or switching power supplies. The instantaneous design (no short-time delay) trips within milliseconds, which is standard for personnel protection but means it may nuisance-trip on high inrush loads like motor starting — check coordination if feeding inductive gear. Mounts on DIN rail (REG) in any position. Depth is 70 mm, which matches the standard 70 mm installation depth of most SENTRON modular devices — no extra clearance needed behind the rail. Supply can enter from top or bottom. The N-left variant means the neutral busbar connects on the left side of the device; verify busbar orientation before wiring. IP20 rating applies only when installed in a distribution board with connected conductors — not for open-panel use.","metaTitle":"Siemens 5SV5311-6KL SENTRON RCCB, 2-pole, 16 A, 30 mA, Type","metaDescription":"Siemens 5SV5311-6KL SENTRON RCCB, 2-pole, 16 A, 30 mA, Type A, 230 V AC, 50 Hz, 6 kA SCCR, DIN rail mount, IP20. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV5311-6KL","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, type A, In: 16 A, 30 mA, Un AC: 230 V, N left","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Variations":"N left","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Product Designation":"RCCB","at AC / rated value":"16 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"A","I2t value / permissible":"58 000 A²·s","at 40 °C / rated value":"16 A","Short-Circuit Current Rating":"6 kA","Number Of Modular Width Units":"2","Product Feature / Silicon-Free":"Yes","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"5 200 A","Tripping Fault Current / Rated Value":"30 mA","Surge Current Resistance / Rated Value":"1 kA","according to IEC 61008-1 / rated value":"0.5 kA","Switching Function / Short-Term Delayed":"No","Value Range / Of The Operating Frequency":"50 Hz","value range / of the supply voltage / at AC":"230 V","Value Range / Of The Supply Voltage Frequency":"50 Hz","Supply Voltage / For Testing Equipment / Minimum":"195 V","Mechanical Service Life (Switching Cycles) / Typical":"2 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8dcee5a7c4d8a6d3f140098183cef20e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=81106&mlfb=5SV5311-6KL"},"ai":{"faq":[{"question":"What is 5SV5311-6KL's listed depth (70 mm) on this component line?","answer":"The depth is 70 mm, which is the standard installation depth for SENTRON modular devices — no extra clearance behind the DIN rail is needed beyond that."},{"question":"What is 5SV5311-6KL's listed width (36 mm) on this component line?","answer":"The width is 36 mm, corresponding to 2 modular width units on a DIN rail. This matches the footprint of most 2-pole SENTRON breakers and RCCBs, so it fits existing busbar and wiring layouts."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV5311-6KL","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV5311-6KL when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}