{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV5314-0","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV5314-0","canonicalUrl":"https://aoctrl.com/siemens/5SV5314-0","factsUrl":"https://aoctrl.com/api/mcp/products/5SV5314-0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, 2-pole, Type AC, In: 40 A, 30 mA, Un AC: 230 V, 6 kA SCCR, DIN rail mount, 2 MW.","salesMarkdown":"The Siemens SENTRON 5SV5314-0 is a 2-pole Type AC residual current circuit breaker (RCCB) rated 40 A with 30 mA trip sensitivity, designed for 230 V AC 50 Hz systems. In a panel with a 6 kA prospective fault current at the bus, this device coordinates — no need for a current-limiting upstream breaker unless the fault level exceeds that figure. The 30 mA residual sensitivity is the standard threshold for personnel protection in most national wiring rules (IEC 60364, UK BS 7671, etc.). The IP20 rating applies only when the distribution board is installed and conductors are connected; outside the enclosure the terminals are not touch-safe, so it must live inside a locked or tool-accessible panel. ## Panel integration Silicon-free construction is confirmed — relevant for potting or conformal-coating processes where silicone contamination must be avoided.","metaTitle":"Siemens SENTRON 5SV5314-0 RCCB, 2-pole Type AC, 40 A 30 mA","metaDescription":"Siemens SENTRON 5SV5314-0 2-pole Type AC RCCB, 40 A rated current, 30 mA trip sensitivity, 230 V AC, 6 kA SCCR. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV5314-0","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, Type AC, In: 40 A, 30 mA, Un AC: 230 V","Grid Spacing":"60 mm","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"6 kA","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"top or bottom","according to IEC 61008-1 rated value":"0.5 kA","Switching Function Short-Term Delayed":"No","Value Range Of The Operating Frequency":"50 Hz","value range of the supply voltage at AC":"230 V","Ambient Temperature During Storage Minimum":"-40 °C","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"195 V","Mechanical Service Life (Operating Cycles) Typical":"2 000","Product Extension Installable Supplementary Devices":"No","Short-Circuit Current Of Series Fuse Maximum Permissible":"63 A","for rated value of the current at AC in hot operating state per pole":"2.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1f24b82f4fe05c269b181085be221e3d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=172191&mlfb=5SV5314-0"},"ai":{"faq":[{"question":"Where can I buy the 5SV5314-0 and get a price?","answer":"The 5SV5314-0 is sourced to order through independent distribution. Submit an RFQ; we confirm availability and current pricing at quote time. No stock count or price is published here because market conditions change daily."},{"question":"What is the 5SV5314-0's depth?","answer":"The listed depth is 70 mm (installation depth also 70 mm). That fits standard 60 mm grid-spacing DIN-rail enclosures with clearance for wiring behind the rail."},{"question":"Will the 5SV5314-0 drop into a panel specified around the 5SY7210-7CC without rewiring?","answer":"Both are 2-pole, 36 mm wide (2 MW), DIN-rail mounted SENTRON devices with the same 70 mm installation depth. The 5SV5314-0 is an RCCB (residual current protection); the 5SY7210-7CC is an MCB (overcurrent protection). They serve different functions — you cannot swap one for the other without changing the circuit protection scheme. Physically they occupy the same footprint, but the wiring and protection coordination must be redesigned."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV5314-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV5314-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}