{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV5412-0","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV5412-0","canonicalUrl":"https://aoctrl.com/siemens/5SV5412-0","factsUrl":"https://aoctrl.com/api/mcp/products/5SV5412-0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON RCCB, 2-pole, Type AC, In: 25 A, 100 mA, Un AC: 230 V, 6 kA SCCR, DIN rail, IP20.","salesMarkdown":"The Siemens 5SV5412-0 is a SENTRON residual current circuit breaker (RCCB) — a 2-pole, Type AC, instantaneous device rated 25 A at 230 V AC, 50 Hz, with a 100 mA trip threshold. That 100 mA rating means it's sized for general fault protection on circuits where a lower 30 mA threshold would cause nuisance tripping from normal leakage (e.g., long cable runs or equipment with inherent leakage). Depth is 70 mm — standard for a 2-pole RCCB in a distribution board. The IP20 rating applies when the board is installed with conductors connected, so it's intended for enclosed panels, not open washdown areas. Supply can enter from top or bottom, which saves time during rework or when the panel layout forces a reverse feed. ## Key approvals and standards Rated according to EN 60898 and IEC 61008-1 at 0.5 kA for the switching capacity under those standards. Overvoltage category III, silicon-free design. The 2,000 mechanical switching cycles typical service life is standard for an RCCB — not a high-cycle contactor, but fine for its protection role.","metaTitle":"Siemens 5SV5412-0 SENTRON RCCB, 25 A, 100 mA, 2-Pole","metaDescription":"Siemens SENTRON 5SV5412-0 RCCB, 25 A, 100 mA, Type AC, 2-pole, 6 kA SCCR, IP20. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV5412-0","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, Type AC, In: 25 A, 100 mA, Un AC: 230 V","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Operating Frequency":"50 Hz","Product Designation":"RCCB","at AC / rated value":"25 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","I2t value / permissible":"58 000 A²·s","at 40 °C / rated value":"25 A","Short-Circuit Current Rating":"6 kA","Number Of Modular Width Units":"2","Product Feature / Silicon-Free":"Yes","acc. to EN 60898 / rated value":"0.5 kA","For Testing Equipment / Minimum":"100 V","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"5 200 kA","Tripping Fault Current / Rated Value":"100 mA","Supply Voltage Frequency / Rated Value":"50 Hz","according to IEC 61008-1 / rated value":"0.5 kA","Switching Function / Short-Term Delayed":"No","size of installation devices / acc. to DIN 43880":"1","Mechanical Service Life (Switching Cycles) / Typical":"2 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f6426bad6c09a56f1e593cdccedb46d0.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=50170&mlfb=5SV5412-0"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SV5412-0?","answer":"Submit an RFQ; we source through independent distribution and confirm pricing and availability at quote time."},{"question":"What is 5SV5412-0's width?","answer":"36 mm, or 2 modular width units on a DIN rail."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV5412-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV5412-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}