{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV5414-0","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV5414-0","canonicalUrl":"https://aoctrl.com/siemens/5SV5414-0","factsUrl":"https://aoctrl.com/api/mcp/products/5SV5414-0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV5414-0, 2-pole RCCB, Type AC, 40 A, 100 mA, 230/400 V AC, 50 Hz, 6 kA, DIN rail.","salesMarkdown":"## Siemens 5SV5414-0 SENTRON RCCB — 40 A, 100 mA, Type AC The Siemens 5SV5414-0 is a 2-pole residual current operated circuit breaker (RCCB) from the SENTRON series, rated 40 A with a 100 mA tripping fault current, Type AC, for 230/400 V AC at 50 Hz networks. It carries a 6 kA short-circuit current rating per IEC 61008-1 and is designed for instantaneous switching — no short-time delay on the residual current detection. The 100 mA trip threshold makes this unit suitable for circuits where a 30 mA device would cause nuisance tripping — typically feeder or submain protection in commercial or industrial distribution boards, not final socket-outlet circuits where 30 mA is the norm for personal protection. The Type AC designation means it detects sinusoidal alternating residual currents only; it will not reliably trip on pulsed DC or smooth DC faults, so it belongs on purely AC loads like lighting, heating, and motor feeders without VFDs or rectified supplies. Mounting position is unrestricted — top or bottom feed accepted. Depth is 70 mm, which matches standard distribution board cutouts; the IP20 rating applies once the distribution board is installed with conductors connected. The 1.6 W power dissipation per pole at rated current should be factored into enclosure thermal calculations, especially in densely populated DIN-rail assemblies. The permissible let-through energy is 58 000 A²·s, and the maximum let-through current is 5 200 A. The silicon-free construction (Product Feature Silicon-Free: Yes) matters for applications where silicone outgassing can contaminate contacts or optical surfaces — common in automotive paint shops or clean-room adjacent panels. ## Integration Notes No auxiliary contact or shunt-trip add-ons are supported (Product Extension Installable Supplementary Devices: No) — this is a standalone RCCB, not a modular accessory platform. The supply voltage for the test circuit is a minimum of 100 V AC. Mechanical service life is 2 000 operating cycles typical — adequate for distribution board duty where the RCCB is operated infrequently (quarterly test button press plus occasional manual isolation). Not rated for frequent switching as a load-break device.","metaTitle":"Siemens 5SV5414-0 SENTRON RCCB, 40 A, 100 mA, Type AC","metaDescription":"Siemens 5SV5414-0 SENTRON 2-pole RCCB, 40 A rated, 100 mA trip, Type AC, 6 kA SCCR, 230/400 V, 50 Hz. DIN rail mount, IP20. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","title":"5SV5414-0","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","description":"Residual current operated circuit breaker, 2-pole, Type AC, In: 40 A, 100 mA, Un AC: 230 V","Grid Spacing":"60 mm","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"40 A","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Product Designation":"RCCB","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","I2t value permissible":"58 000 A²·s","Residual Current Type":"AC","at 40 °C rated value":"40 A","Product Feature Silicon-Free":"Yes","Short-Circuit Current Rating":"6 kA","Number Of Modular Width Units":"2","Position Of Power Supply Cord":"top or bottom","Let-Through Current Permissible":"5 200 A","Tripping Fault Current Rated Value":"100 mA","according to IEC 61008-1 rated value":"0.5 kA","Switching Function Short-Term Delayed":"No","Value Range Of The Operating Frequency":"50 Hz","value range of the supply voltage at AC":"230/400 V","Value Range Of The Supply Voltage Frequency":"50 Hz","Supply Voltage For Testing Equipment Minimum":"100 V","Mechanical Service Life (Operating Cycles) Typical":"2 000","Product Extension Installable Supplementary Devices":"No","Short-Circuit Current Of Series Fuse Maximum Permissible":"63 A","for rated value of the current at AC in hot operating state per pole":"1.6 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/025f22516278ea8d2481353d7a13b5f2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=33732&mlfb=5SV5414-0"},"ai":{"faq":[{"question":"What is the difference between 5SV5414-0 and 5SL4363-7?","answer":"The 5SL4363-7 is a miniature circuit breaker (MCB), not an RCCB — it provides overcurrent and short-circuit protection only, with no residual current detection. The 5SV5414-0 provides earth leakage protection only (no overcurrent protection). They are complementary devices, not substitutes; a typical installation uses an MCB upstream or in series with an RCCB for full protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV5414-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV5414-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}