{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV5416-0","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV5416-0","canonicalUrl":"https://aoctrl.com/siemens/5SV5416-0","factsUrl":"https://aoctrl.com/api/mcp/products/5SV5416-0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 5SV5416-0, RCCB, 2-pole, Type AC, 63 A, 100 mA, 230 V AC, 50 Hz, 6 kA, DIN rail mount.","salesMarkdown":"## What this RCCB does on the line Depth is 70 mm — the same as the installation depth, so no extra clearance needed behind the rail. Supply can enter from top or bottom. The IP20 rating applies when installed in a distribution board with conductors connected — standard for enclosed panel use. The 6 kA SCCR (IEC 61008-1 / EN 60898) is the maximum prospective fault current the device can safely interrupt. The 100 mA sensitivity is higher than the typical 30 mA for personal shock protection; it's used where the goal is fire protection or equipment protection on circuits with higher natural leakage. The I²t let-through of 110,000 A²s and peak let-through current of 7,100 A are the energy and current the RCCB allows downstream during a fault — useful for coordinating with downstream MCBs.","metaTitle":"Siemens 5SV5416-0 SENTRON RCCB, 63 A, 100 mA, Type AC, 2-pol","metaDescription":"Siemens 5SV5416-0 SENTRON RCCB, 63 A rated, 100 mA trip, Type AC, 2-pole, 6 kA SCCR, 50 Hz, DIN rail mount. Active lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"70 mm","Width":"36 mm","Height":"90 mm","Maximum":"45 °C","Minimum":"-25 °C","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Maximum Permissible":"75 °C","Minimum Permissible":"-40 °C","Operating Frequency":"50 Hz","Product Designation":"RCCB","at AC / rated value":"63 A","protection class IP":"IP20, if the distribution board is installed, with connected conductors","Overvoltage Category":"III","Design Of The Product":"Instantaneous","Residual Current Type":"AC","I2t value / permissible":"110 000 A²·s","at 40 °C / rated value":"63 A","Short-Circuit Current Rating":"6 kA","Number Of Modular Width Units":"2","Product Feature / Silicon-Free":"Yes","acc. to EN 60898 / rated value":"0.8 kA","For Testing Equipment / Minimum":"100 V","Position / Of Power Supply Cord":"top or bottom","Let-Through Current / Permissible":"7 100 kA","Tripping Fault Current / Rated Value":"100 mA","Supply Voltage Frequency / Rated Value":"50 Hz","according to IEC 61008-1 / rated value":"0.8 kA","Switching Function / Short-Term Delayed":"No","size of installation devices / acc. to DIN 43880":"1","Mechanical Service Life (Switching Cycles) / Typical":"2 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cb580f56583bd55b660e7a26fa5d9d1f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=14686&mlfb=5SV5416-0","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV5416-0/alternatives.json"},"ai":{"faq":[{"question":"What is the 5SV5416-0 used for?","answer":"It is a 2-pole Type AC RCCB rated 63 A / 100 mA, used for residual current protection on 230 V AC, 50 Hz single-phase circuits. The 100 mA sensitivity suits fire protection or equipment protection on circuits with higher natural leakage current."},{"question":"How do I get pricing and availability for 5SV5416-0?","answer":"Submit an RFQ through this listing. The part is sourced to order through independent distribution; current pricing and stock position are confirmed at quote time."},{"question":"Does 5SV5416-0 fit a panel designed for 5SL6550-7BB?","answer":"Both are 2-pole, 36 mm wide, 90 mm tall, DIN rail mounted, with the same 70 mm installation depth. The 5SL6550-7BB is an MCB, not an RCCB, so the function differs, but the mechanical footprint is identical — no rewiring of the DIN rail or enclosure cutout is needed."},{"question":"What compliance documentation does Siemens provide for 5SV5416-0?","answer":"The part carries IEC 61008-1 and EN 60898 ratings (0.8 kA Icn). The SENTRON series typically includes CE, UKCA, and EAC declarations; specific certificates should be requested with the RFQ. The product is silicon-free and rated for overvoltage category III."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV5416-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV5416-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}