{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV6016-6KK10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV6016-6KK10","canonicalUrl":"https://aoctrl.com/siemens/5SV6016-6KK10","factsUrl":"https://aoctrl.com/api/mcp/products/5SV6016-6KK10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON AFDD-MCB combination, 1P+N, 10 A, B-curve, 6 kA, 1 MW modular width, DIN rail mount.","salesMarkdown":"## Arc-fault and overcurrent in one 18 mm slot The Siemens 5SV6016-6KK10 is a SENTRON AFDD-MCB combination — an arc-fault detection device (AFDD) and miniature circuit breaker (MCB) rolled into a single 1 MW (18 mm wide) compact unit. It protects a 230 V AC, 50 Hz, 1P+N final circuit at 10 A with a B-curve trip characteristic, and interrupts fault currents up to 6 kA per both EN 60898-1 and IEC 60947-2. That 6 kA rating is the same under either standard, so you don't have to derate or double-check which code governs the installation. The B-curve (trips at 3–5× In) means this unit is sized for resistive or light inductive loads — lighting, small heaters, control transformers — not motor starting or high-inrush gear. The 1P+N design switches the line conductor and switches the neutral, but does not protect the neutral — the neutral pole is a switching pole only. ## Mounting and environment Depth is 68.5 mm, installation depth 70 mm — that extra 1.5 mm accounts for the DIN rail clip clearance behind the panel door. IP20 with conductors connected means it's finger-safe once wired, but not protected against water ingress — keep it inside the enclosure.","metaTitle":"Siemens 5SV6016-6KK10 SENTRON AFDD-MCB, 10A B-curve, 6kA","metaDescription":"Siemens SENTRON 5SV6016-6KK10 AFDD-MCB combination, 1P+N, 10A, B-curve, 6kA breaking capacity per EN 60898-1/IEC 60947-2. Active production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"68.5 mm","Width":"18 mm","title":"5SV6016-6KK10","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"AFDD-MCB-Combination 230V, 6kA, 1+N, B, 10A Compact (1MW)","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"AFDD-MCB combination","protection class IP":"IP20, with connected protective device and conductors","Overvoltage Category":"III","Design Of The Product":"Compact unit","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"any","Tripping Characteristic Class":"B","according to EN 60898-1 rated value":"6 000 A","according to IEC 60947-2 rated value":"6 000 A","Switching Function Short-Term Delayed":"No","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50Hz","Ambient Temperature With Relative Humidity 95%":"55 °C","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.66 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2e2939b7046519e3be2f5a5be6711c6b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1108718&mlfb=5SV6016-6KK10"},"ai":{"faq":[{"question":"What is 5SV6016-6KK10's depth and width?","answer":"Depth is 68.5 mm (installation depth 70 mm) and width is 18 mm (1 modular width unit)."},{"question":"Can 5SV6016-6KK10 replace a standard MCB like 5SY4116-7CV in an existing panel?","answer":"Not directly — the 5SV6016-6KK10 is an AFDD-MCB combination (arc-fault detection plus overcurrent) while the 5SY4116-7CV is a standard MCB. Both mount on DIN rail at 18 mm width, but the AFDD adds arc-fault detection electronics that may require different wiring (neutral switching) and has a 6 kA breaking capacity versus 15 kA for the 5SY4116-7CV. Check if the circuit requires arc-fault protection before substituting."},{"question":"Where can I buy 5SV6016-6KK10?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV6016-6KK10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV6016-6KK10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}