{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV6016-6KP25","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV6016-6KP25","canonicalUrl":"https://aoctrl.com/siemens/5SV6016-6KP25","factsUrl":"https://aoctrl.com/api/mcp/products/5SV6016-6KP25","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON AFDD-MCB combination, 230V AC, 6kA, 1+N, B-curve, 25A, compact 1MW pigtail, 18mm wide.","salesMarkdown":"The Siemens SENTRON 5SV6016-6KP25 is an arc-fault detection device (AFDD) and miniature circuit breaker (MCB) combined into a single compact unit — it detects series and parallel arcing faults in final circuits and simultaneously provides overcurrent and short-circuit protection, all in one 18 mm wide module that snaps onto a DIN rail. Breaking capacity is 6 kA per both EN 60898-1 and IEC 60947-2 — that means it can safely interrupt a fault current up to 6,000 A without welding its contacts or failing catastrophically, which covers the majority of domestic and small commercial distribution boards where the prospective short-circuit current stays under that threshold. Rated at 25 A, the unit handles a continuous load up to that current; the 1+N pole configuration switches both phase and neutral, with the neutral pole switching but not protecting. Snaps onto a DIN rail (REG profile) in any mounting position. At 18 mm wide (1 modular width unit) and 68.5 mm deep, it fits standard distribution board cutouts; the 70 mm installation depth accounts for the pigtail and wiring space behind the rail. Halogen-free and silicon-free construction meets environmental and outgassing requirements for sensitive installations like data centers or clean rooms. The unit is designed and tested to EN 60898-1 and IEC 60947-2; standard Siemens SENTRON documentation (declaration of conformity, CE, RoHS, REACH) is available on request.","metaTitle":"Siemens 5SV6016-6KP25 SENTRON AFDD-MCB, 230V, 6kA, B-25A","metaDescription":"Siemens SENTRON 5SV6016-6KP25 AFDD-MCB combination, 230V AC, 6kA breaking capacity, B-curve, 25A, 1+N pole, 18mm wide. Active production. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"68.5 mm","Width":"18 mm","title":"5SV6016-6KP25","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"AFDD-MCB-combination 230V, 6kA, 1+N, B, 25A compact (1MW) pigtail","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"AFDD-MCB combination","protection class IP":"IP20, with connected protective device and conductors","Overvoltage Category":"III","Design Of The Product":"Compact unit","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"any","Tripping Characteristic Class":"B","according to EN 60898-1 rated value":"6 000 A","according to IEC 60947-2 rated value":"6 000 A","Switching Function Short-Term Delayed":"No","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50Hz","Ambient Temperature With Relative Humidity 95%":"55 °C","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.45 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2e2939b7046519e3be2f5a5be6711c6b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1268759&mlfb=5SV6016-6KP25"},"ai":{"faq":[{"question":"Where can I buy 5SV6016-6KP25 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote on your quantity."},{"question":"What is the depth of 5SV6016-6KP25?","answer":"The 5SV6016-6KP25 has a depth of 68.5 mm (70 mm installation depth accounting for wiring space behind the DIN rail)."},{"question":"Will 5SV6016-6KP25 drop into a panel specified for 5SY4116-7CV without rewiring?","answer":"No — the 5SV6016-6KP25 is an AFDD-MCB combination (arc-fault detection plus overcurrent protection) while the 5SY4116-7CV is a standard MCB without arc-fault detection. The 5SV6016-6KP25 also has a 1+N pole configuration (switched neutral) versus the 1-pole 5SY4116-7CV, so wiring differs. Both are 18 mm wide and DIN-rail mountable, but the circuit design and protective function are not drop-in interchangeable."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV6016-6KP25","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV6016-6KP25 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}