{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV6016-6MC16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV6016-6MC16","canonicalUrl":"https://aoctrl.com/siemens/5SV6016-6MC16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV6016-6MC16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON AFDD-MCB combination, 5SV6016-6MC16, 1P+N, B-characteristic, 6 kA breaking capacity, integrated metering, 1 MW wide, DIN rail mount.","salesMarkdown":"The Siemens 5SV6016-6MC16 is a SENTRON AFDD-MCB combination — a single compact unit that packs arc-fault detection, overcurrent protection, and energy metering into one 18 mm-wide module (one modular width). It protects a 1P+N circuit with a B tripping characteristic and a 6 000 A breaking capacity per EN 60898-1, meaning it clears short-circuit faults up to 6 kA at 230 V AC without needing an upstream fuse backup in most residential or light-commercial panels. ## Integrated metering — what you can read off the front Unlike a plain MCB, this unit includes a voltmeter, ammeter, wattmeter, frequency meter, and reactive-power meter — all visible on the front display. Accuracy for current and voltage is 0.5 %, for active power 1 %, per IEC 61557-12, IEC 62053-22, and IEC 62053-23. The display cycles through voltage, current, active/apparent/reactive power, active energy, line frequency, power factor, temperature, switching cycles, operating hours, tripping events, and warnings — enough data to trend a circuit's health without a separate power meter. ## Where it fits — panel integration and environment Depth is 68.5 mm, installation depth 70 mm — it clears most shallow enclosures. Rated IP40 on the front, IP20 at the rear (with conductors and protective device connected). ## Compliance and ruggedness notes Tested for shock and vibration per IEC 61373, so it holds up in rail-vehicle or mobile-equipment panels. Supports a wireless protocol for data readout — no separate communication module needed to pull metering data off the unit.","metaTitle":"Siemens 5SV6016-6MC16 SENTRON AFDD-MCB, 1P+N, B-char, 6 kA","metaDescription":"Siemens SENTRON 5SV6016-6MC16 AFDD-MCB combination, 1P+N, B-curve, 6 kA per EN 60898-1. Integrated metering (V, A, W, Hz, PF). Current lifecycle. Sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"68.5 mm","Width":"18 mm","title":"5SV6016-6MC16","Height":"90 mm","Ammeter":"Yes","Maximum":"75 °C","Minimum":"-40 °C","Rear Side":"IP20","Voltmeter":"Yes","Wattmeter":"Yes","For Shocks":"IEC 61373","description":"AFDD-MCB-Combination Measuring, Communication AC 230V 6kA, 1+N pole, B, 16A Please consider Radio approval! List of countries: see Certificates","Halogen-Free":"Yes","On The Front":"IP40","Silicon-Free":"Yes","Design Of Pole":"1P+N","Frequency Meter":"Yes","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"AFDD-MCB combination","protection class IP":"IP20, with connected protective device and conductors","Overvoltage Category":"III","Reactive Power Meter":"Yes","Design Of The Product":"Compact unit","Protocol Is Supported":"wireless protocol","Standards For Error Limits":"based on IEC61557-12, IEC62053-22, IEC62053-23","For Measured Variable Current":"0.5 %","For Measured Variable Voltage":"0.5 %","For Testing Equipment Minimum":"195 V","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"any","Tripping Characteristic Class":"B","Type Of Measured Value Detection":"seamless","For Measured Variable Active Power":"1 %","Status Display Of The Measured Data":"voltage, current, active power, apparent power, reactive power, active energy, line frequency, power factor, temperature, switching cycles, operating hours, tripping, warnings","according to EN 60898-1 rated value":"6 000 A","For Measured Variable Apparent Power":"1 %","For Measured Variable Reactive Power":"1 %","according to IEC 60947-2 rated value":"6 000 A","Guideline Via Radio-Controlled System":"2014/53/EU","Switching Function Short-Term Delayed":"No","For Measured Variable Electrical Energy":"1 %","Measurable Line Frequency Initial Value":"45 Hz","Type Of Voltage Of The Operating Voltage":"AC","Frequency With Radio Transmission Maximum":"2 483.5 MHz","Frequency With Radio Transmission Minimum":"2 400 MHz","Measurable Line Frequency Full-Scale Value":"60 Hz","Measuring Category For Voltage Measurement":"CATIII according to IEC 61010-2-030","Measuring Procedure For Current Measurement":"TRMS","Measuring Procedure For Voltage Measurement":"TRMS","Value Range Of The Supply Voltage Frequency":"50Hz","Ambient Temperature With Relative Humidity 95%":"55 °C","Apparent Power Consumption Of The Power Supply":"0.4 VA","For Environmental Sinusoidal Oscillation Check":"IEC 60068-2-6","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"2.4 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2e2939b7046519e3be2f5a5be6711c6b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1445919&mlfb=5SV6016-6MC16"},"ai":{"faq":[{"question":"What metering values does the 5SV6016-6MC16 display?","answer":"Voltage, current, active/apparent/reactive power, active energy, line frequency, power factor, temperature, switching cycles, operating hours, tripping events, and warnings."},{"question":"Does 5SV6016-6MC16 drop into a panel specified for 5SL3116-6MB?","answer":"Both mount on standard DIN rail, but the 5SV6016-6MC16 is an AFDD-MCB combination with integrated metering, while the 5SL3116-6MB is a standard MCB without arc-fault detection or metering. The footprint is the same 1 MW width, so mechanical fit is identical, but the wiring and functional requirements differ — the AFDD needs a neutral connection for arc-fault detection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV6016-6MC16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV6016-6MC16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}