{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV6016-7KK06","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV6016-7KK06","canonicalUrl":"https://aoctrl.com/siemens/5SV6016-7KK06","factsUrl":"https://aoctrl.com/api/mcp/products/5SV6016-7KK06","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON AFDD-MCB combination, 230 V AC, 6 kA, 1P+N, C, 6 A, compact 1 MW unit.","salesMarkdown":"## Arc-fault detection in one module width The Siemens 5SV6016-7KK06 is a SENTRON AFDD-MCB combination — an arc-fault detection device and miniature circuit breaker integrated into a single compact unit, rated 230 V AC at 50 Hz with a C-curve 6 A trip characteristic and 6 kA breaking capacity per both EN 60898-1 and IEC 60947-2. It occupies one modular width (18 mm) on a DIN rail, making it a space-efficient choice for final circuits where both overcurrent protection and series arc-fault detection are required in a single housing. The 6 kA breaking capacity (Icn = 6 kA per EN 60898-1, Icu = 6 kA per IEC 60947-2) is the standard domestic and light-commercial interrupting rating — adequate for most final sub-distribution boards where the prospective short-circuit current at the point of installation does not exceed 6 kA. The 1P+N design switches the line conductor and provides neutral switching, which is required in some regional wiring regulations for arc-fault protection devices to ensure the arc is fully extinguished. The unit is halogen-free and silicon-free, a material constraint often specified for clean-room, aerospace, or semiconductor-adjacent installations where outgassing must be controlled. Power loss is 0.87 W per pole in hot operating state at rated current — negligible for thermal coordination in a populated enclosure, but worth noting when calculating cumulative heat rise in a sealed distribution board. ## Deployment context Snap-on DIN rail (REG) mounting, any orientation, IP20 with connected protective device and conductors — intended for installation inside a distribution board or enclosure, not for wet or outdoor locations.","metaTitle":"Siemens 5SV6016-7KK06 SENTRON AFDD-MCB, 6kA C 6A 1P+N","metaDescription":"Siemens SENTRON 5SV6016-7KK06 AFDD-MCB combination, 230V AC, 6kA breaking capacity, C-curve 6A, 1P+N, 1MW wide. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"68.5 mm","Width":"18 mm","title":"5SV6016-7KK06","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","description":"AFDD-MCB-Combination 230V, 6kA, 1+N, C, 6A Compact (1MW)","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","Product Designation":"AFDD-MCB combination","protection class IP":"IP20, with connected protective device and conductors","Overvoltage Category":"III","Design Of The Product":"Compact unit","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"any","Tripping Characteristic Class":"C","according to EN 60898-1 rated value":"6 000 A","according to IEC 60947-2 rated value":"6 000 A","Switching Function Short-Term Delayed":"No","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50Hz","Ambient Temperature With Relative Humidity 95%":"55 °C","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","power loss [W] for rated value of the current at AC in hot operating state per pole":"0.87 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2e2939b7046519e3be2f5a5be6711c6b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1108725&mlfb=5SV6016-7KK06"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 5SV6016-7KK06?","answer":"Pricing and availability are confirmed at quote time against an RFQ. Submit a request through the storefront; we source through independent distribution channels and provide a current quote."},{"question":"Will 5SV6016-7KK06 drop into a panel that was specified around 5SY4101-7CV without rewiring?","answer":"No — the 5SY4101-7CV is a 1-pole miniature circuit breaker without arc-fault detection, while the 5SV6016-7KK06 is a 1P+N AFDD-MCB combination. Both mount on DIN rail and share the same 18 mm width, but the 5SV6016-7KK06 requires a neutral connection and serves a different protection function (arc-fault plus overcurrent vs. overcurrent only). They are not drop-in substitutes."},{"question":"What is 5SV6016-7KK06's listed depth (68.5 mm) on this component line?","answer":"The listed depth is 68.5 mm, with an installation depth of 70 mm. The unit is 90 mm tall and 18 mm wide (1 modular width)."},{"question":"What compliance documentation does this brand provide for 5SV6016-7KK06 (RoHS, REACH, UL, IEC)?","answer":"The device is rated per EN 60898-1 and IEC 60947-2, and is halogen-free and silicon-free. For specific RoHS/REACH/UL declarations, consult the Siemens SENTRON documentation package available via the manufacturer's support portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV6016-7KK06","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV6016-7KK06 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}