{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV6016-7KK16","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV6016-7KK16","canonicalUrl":"https://aoctrl.com/siemens/5SV6016-7KK16","factsUrl":"https://aoctrl.com/api/mcp/products/5SV6016-7KK16","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON AFDD-MCB combination, 230 V AC, 16 A, C-curve, 1P+N, 6 kA, compact 1 MW unit.","salesMarkdown":"It is rated 16 A at 230 V AC, 50 Hz, with a C tripping characteristic, and provides a 6 000 A breaking capacity per both EN 60898-1 and IEC 60947-2. The 1P+N pole design and 18 mm width (1 modular unit) let it slot into standard DIN-rail distribution boards without crowding adjacent ways. ## Arc-fault detection — the so-what This is not a plain MCB. The integrated AFDD detects series arcs (down to 2 A) and parallel arcs (down to 50 A) that a standard breaker would not see — the kind of low-current arcing that can start a fire inside a cable joint or a loose terminal. It is designed to trip on those arcs while still providing full overcurrent and short-circuit protection.","metaTitle":"Siemens 5SV6016-7KK16 SENTRON AFDD+MCB, C-16A, 1P+N, 6kA","metaDescription":"Siemens 5SV6016-7KK16 SENTRON arc-fault detection device (AFDD) combined with MCB. 16 A, C-curve, 1P+N, 6 kA breaking capacity per EN 60898-1. Active production. Sourced to order a","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"68.5 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","at AC rated value":"230 V","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","protection class IP":"IP20, with connected protective device and conductors","Overvoltage Category":"III","Design Of The Product":"Compact unit","Number Of Modular Width Units":"1","Position Of Power Supply Cord":"any","Tripping Characteristic Class":"C","according to EN 60898-1 rated value":"6 000 A","according to IEC 60947-2 rated value":"6 000 A","Switching Function Short-Term Delayed":"No","operational current at AC rated value":"16 A","Type Of Voltage Of The Operating Voltage":"AC","Value Range Of The Supply Voltage Frequency":"50Hz","Ambient Temperature With Relative Humidity 95%":"55 °C","Mechanical Service Life (Operating Cycles) Typical":"10 000","Product Extension Installable Supplementary Devices":"Yes","In The Event Of Electrical Arcs In Series With The Load Maximum":"16 A","In The Event Of Electrical Arcs In Series With The Load Minimum":"2 A","In The Event Of Electrical Arcs In Parallel With The Load Maximum":"500 A","In The Event Of Electrical Arcs In Parallel With The Load Minimum":"50 A","power loss [W] for rated value of the current at AC in hot operating state per pole":"1.81 W"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2e2939b7046519e3be2f5a5be6711c6b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1108728&mlfb=5SV6016-7KK16","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV6016-7KK16/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 5SV6016-7KK16 and get a price?","answer":"The 5SV6016-7KK16 is sourced to order against an RFQ through independent distribution with full traceability. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"Will the 5SV6016-7KK16 drop into a panel specified for the 5SL6120-7?","answer":"Both are 18 mm wide, 1-module SENTRON units that snap onto the same DIN rail, but the 5SV6016-7KK16 is an AFDD-MCB combination (1P+N, 16 A, C-curve, 6 kA) while the 5SL6120-7 is a plain MCB (1P, 16 A, C-curve, 6 kA). The AFDD adds arc-fault detection and requires the neutral connection (1P+N), so the wiring differs — it is not a direct electrical swap without verifying the circuit design."},{"question":"What is the 5SV6016-7KK16's depth?","answer":"The 5SV6016-7KK16 has a depth of 68.5 mm and an installation depth of 70 mm, fitting standard distribution board enclosures."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV6016-7KK16","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV6016-7KK16 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}