{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"5SV6016-7KP10","brand":"Siemens","brandSlug":"siemens","productSlug":"5SV6016-7KP10","canonicalUrl":"https://aoctrl.com/siemens/5SV6016-7KP10","factsUrl":"https://aoctrl.com/api/mcp/products/5SV6016-7KP10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON AFDD-MCB combination, 1P+N, C-curve 10 A, 6 kA, 230 V AC, compact 1 MW unit, halogen-free, silicon-free.","salesMarkdown":"It protects a single-phase 230 V AC final circuit at 10 A with a C-curve tripping characteristic, and it interrupts fault currents up to 6 kA per both EN 60898-1 and IEC 60947-2. Snaps onto DIN rail (REG) and occupies a single modular width unit (18 mm). Mounting position is unrestricted — install it any orientation in the enclosure. Installation depth is 70 mm; the overall body depth is 68.5 mm, so it sits flush with the front of a standard 70 mm deep distribution board. Rated for 10 000 mechanical switching cycles typical. Halogen-free and silicon-free construction. Degree of pollution 2, overvoltage category III. Supply frequency 50 Hz only. Minimum testing voltage 195 V. No short-time delayed switching function.","metaTitle":"Siemens 5SV6016-7KP10 SENTRON AFDD+MCB, 10A C-curve 1P+N 6kA","metaDescription":"Siemens SENTRON 5SV6016-7KP10 AFDD-MCB combination, 10A C-curve, 1P+N, 230V AC, 6kA breaking capacity per EN 60898-1/IEC 60947-2. Active production, available to order. Request quo","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"68.5 mm","Width":"18 mm","Height":"90 mm","Maximum":"75 °C","Minimum":"-40 °C","Halogen-Free":"Yes","Silicon-Free":"Yes","Design Of Pole":"1P+N","Number Of Poles":"2","lifecycle_stage":"current","Fastening Method":"DIN rail (REG)","Mounting Position":"any","Installation Depth":"70 mm","Product Brand Name":"SENTRON","Degree Of Pollution":"2","at AC / rated value":"230 V","protection class IP":"IP20, with connected protective device and conductors","Overvoltage Category":"III","Design Of The Product":"Compact unit","Number Of Modular Width Units":"1","Tripping Characteristic Class":"C","For Testing Equipment / Minimum":"195 V","Position / Of Power Supply Cord":"any","according to EN 60898-1 / rated value":"6 000 A","according to IEC 60947-2 / rated value":"6 000 A","Switching Function / Short-Term Delayed":"No","operational current / at AC / rated value":"10 A","Type Of Voltage / Of The Operating Voltage":"AC","Value Range / Of The Supply Voltage Frequency":"50Hz","Ambient Temperature / With Relative Humidity 95%":"55 °C","Mechanical Service Life (Switching Cycles) / Typical":"10 000","In The Event Of Electrical Arcs In Series With The Load / Maximum":"10 A","In The Event Of Electrical Arcs In Series With The Load / Minimum":"2 A","In The Event Of Electrical Arcs In Parallel With The Load / Maximum":"500 A","In The Event Of Electrical Arcs In Parallel With The Load / Minimum":"50 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2e2939b7046519e3be2f5a5be6711c6b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1268779&mlfb=5SV6016-7KP10","alternativesUrl":"https://aoctrl.com/api/mcp/products/5SV6016-7KP10/alternatives.json"},"ai":{"faq":[{"question":"What is the closest second-source to 5SV6016-7KP10?","answer":"There is no direct second-source for this AFDD-MCB combination. The nearest functional peer is the standard MCB 5SY3025-7KL (25 A C-curve, 4.5 kA), but it lacks arc-fault detection and has different breaking capacity and current rating. Verify the circuit protection requirements before substituting."},{"question":"Will 5SV6016-7KP10 drop into a panel spec'd for 5SY3025-7KL?","answer":"Mechanically yes — both are 18 mm wide, DIN-rail mount, 70 mm installation depth. Electrically no — the AFDD adds a neutral pigtail connection and the internal wiring differs. The 5SV6016-7KP10 also has a lower 10 A rating vs 25 A on the 5SY3025-7KL. Panel re-wiring and circuit re-evaluation are required."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/5SV6016-7KP10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/5SV6016-7KP10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}